WARNING: Never use an open

flame to check for a leak. Apply a
mixture of liquid soap and water
to all joints. Bubbles forming
show a leak. Correct all leaks at
once.

WARNING: Test all gas pip-

ing and connections for leaks
after installing or servicing. Cor-
rect all leaks at once.

CHECKING GAS
CONNECTIONS

Pressure Testing Gas Supply
Piping System

Test Pressures In Excess Of 1/2
PSIG

1.

Disconnect heater and its individual
manual shutoff valve from gas supply
piping system. Pressures in excess of
1/2 psig will damage heater regulator.

2.

Cap off open end of gas pipe where
manual shutoff valve was connected.

3.

Pressurize supply piping system by ei-
ther using compressed air or opening
main gas valve located on or near gas
meter.

4.

Check all joints of gas supply piping
system. Apply mixture of liquid soap
and water to gas joints. Bubbles form-
ing show a leak.

5.

Correct all leaks at once.

6.

Reconnect heater and manual shutoff
valve to gas supply. Check reconnected
fittings for leaks.

INSTALLATION

Continued

Test Pressures Equal To or
Less Than 1/2 PSIG

1.

Close manual shutoff valve (see Fig-
ure 15).

2.

Pressurize supply piping system by ei-
ther using compressed air or opening
main gas valve located on or near gas
meter.

Figure 15 - Manual Shutoff Valve

ON

POSITION

OFF

POSITION

Open

Closed

Manual
Shutoff
Valve

Figure 16 - Checking Gas Joints

Gas Meter

Manual
Shutoff
Valve

Thermostat Gas
Valve or Control
Valve Location

3.

Check all joints from gas meter to
manual shutoff valve (see Figure 16).
Apply mixture of liquid soap and wa-
ter to gas joints. Bubbles forming show
a leak.

4.

Correct all leaks at once.

Pressure Testing Heater Gas
Connections

1.

Open manual shutoff valve (see Fig-
ure 15).

2.

Open main gas valve located on or near
gas meter.

3.

Make sure control knob of heater is in
the OFF position.

4.

Check all joints from manual shutoff
valve to thermostat gas valve (thermo-
stat-controlled models) or control valve
(manually-controlled models) (see Fig-
ure 16). Apply mixture of liquid soap
and water to gas joints. Bubbles form-
ing show a leak.

5.

Correct all leaks at once.

6.

Light heater (see Operating Heater,
pages 14 through 16). Check all other
internal joints for leaks.

7.

Turn off heater (see To Turn Off Gas to
Appliance
, page 15 [thermostat-
controlled models] or page 16 [manu-
ally-controlled models]).