Pca-com, Power connection for flx-bc with braid only, 76mm (3”) braid – Thermon PCA-COM User Manual

Page 5: Tape provided separately ul label, Cut and remove primary insulation jacket, Skive outside of black matrix

background image

4

PCA-COM

3.3.

Feed cable and ground lead through

expediter base as shown. Feed cable

and ground lead through grommet (above

the crimp).

3.2.

Trim braid to approximately 76mm (3”).

Crimp 12/10 AWG compression lug to

ground braid and ground lead.

3.1.

Separate braid strands at edge

of overjacket and pull cable through

opening.

Ground Lead

Wire

12/10 AWG

Crimp

Expediter

Base

Grommet

Ground

Lead

8AWG Crimp

Cable

152mm

(6”)

Power connection for FLX-BC with braid only.

76mm

(3”)

Braid

3.4.

Slide expediter toward pipe and route

cable through base, grommet, and NPT

threaded cap. Secure cap to base with the

captive screws.

3.5.

Mount expediter to pipe using two (2)

circumferential bands of 19mm (3/4”)

wide tape.

3.6.

Place UL® label provided as shown,

locate on opposite side from rectangular

side opening.

Pip

e H

ea

tin

g C

ab

le 1

34

N

HS

X

®

or

FL

X™

H

ea

tin

g C

ab

le S

ys

tem

Ins

tall

C

ab

le p

er N

EC

A

rti

cle

42

7

Th

erm

on

M

an

ufactu
rin

g C

o.

10

0

Th

erm

on

D

r., San Marco

s,

Te

xas 7866

6

1-8

00

-7

30

-4

32

8

P

N

2

74

00

Tape Provided

Separately

UL Label

3.7.

Cut and remove primary insulation jacket.

3.8.

Skive outside of black matrix.

3.9.

Cut V-Notch in matrix and pull bus wires

from matrix. Cut and remove center

matrix.

Do not cut bus wire strands.

117mm

(4-5/8”)

Bus Wire

Primary Insulation

Ground Lead

Matrix

Ground Lead

Ground Lead

Ground Lead

Black Matrix