background image

Kit Contents . . .

Tools Required . . .

Certifications/Approvals . . .

1

2

3

4

5

Item

Quantity

Description

1

1

Expediter Assembly
Locknut
Gasket
1” NPT Threaded Cap
Grommet
Expediter Base

2

1

RTV Tube

3

1

Power Connection Boot

4

1

End Cap ET-6 (FLX-OJ and HSX Cable)

5

1

End Cap ET-8 (FLX-BC Cable)

6

1

12 AWG Green Ground Lead

7

1

End Termination Caution Label

8

1

UL Label

9

1

8 awg Splice Lug

10

1

12/10 awg Splice Lug

6

7

The following installation procedures are suggested guidelines
for the installation of Thermon’s PCA-COM connection systems.
They are not intended to preclude the use of other methods and
good engineering or field construction practices.

Receiving, Storing and Handling . . .
1. Inspect materials for damage incurred during shipping.
2. Report damages to the carrier for settlement.
3. Identify parts against the packing list to ensure the proper

type and quantity have been received.

4. Store in a dry location.

Installation Precautions . . .
• To minimize the potential for arcing and fire caused by product

damage or improper installation use ground-fault protection.
The National Electrical Code (NEC) and Canadian Electrical Code
(CEC) require ground-fault protection of equipment for each
branch circuit supplying electric heat tracing.

• Installation must comply with Thermon requirements and

be installed in accordance with the NEC, CEC, or any other
applicable national and local codes.

• De-energize all power sources before opening enclosure.
• Keep ends of heating cable and kit components dry before and

during installation.

• Component approvals and performance ratings are based on

the use of Thermon specified parts only. User supplied power
connection fittings must be listed or certified for intended use.

• The kit instructions should be used in conjunction with the

installation instructions for the heating cable and other accessory
items.

Pipe Heating Cable 134N

HSX

®

or FLX™ Heating Cable System

Install Cable per NEC Article 427

Thermon Manufacturing Co.

100 Thermon Dr., San Marcos, Texas 78666

1-800-730-4328 PN 27400

8

9

PCA-COM Power Connection and End Termination Kit

1