beautypg.com

Fak-5 and fak-5l: tee splice, Installation procedures – Thermon FAK-5 User Manual

Page 2

background image

FAK-5 and FAK-5L: Tee Splice Kit . . .

The FAK-5 and FAK-5L: Tee Splice Kits are designed to make a
waterproof seal over the end of TubeTrace or ThermoTube at the
splice connections. Review FAK-5 and FAK-5L instructions prior to
installation. Kit will make one splice connection (Tube fi ttings not
included). See separate instructions for details on splicing heating
cables.

Receiving, Storing and Handling . . .
1. Inspect materials for damage incurred during shipping.

2. Report damages to the carrier for settlement.

3. Identify parts against the packing list to ensure the proper

type and quantity has been received.

4. Store in dry location.

FAK-5 and FAK-5L: Tee Splice

INSTALLATION PROCEDURES

Item

Quantity

Description

1

1

Tee Splice Cover (Top)

2

1

Tee Splice Cover (Bottom)

3

8/14

Pan-Head S.S. Screws, #10-32 x .75

4

8/14

KEPT S.S. Nuts, #10-32

5

1

Heat Refl ective Tape

6

1

Glass Fiber Tape

7

2

RTV Sealant Tube

1

3

4

6

5

7

Tools Required . . .

Hacksaw

Screwdriver

FAK-5 and FAK-5L: Tee Splice Kit Contents . . .

2

1

Installation Precautions . . .

• To minimize the potential for arcing and ground-fault protection.

The National Electrical Code (NEC) and Canadian Electrical Code
(CEC) require ground-fault protection of equipment for each
branch circuit supplying electric heat tracing.

• Installation must comply with Thermon requirements and be

installed in accordance with the NEC, CEC, or any other applicable
national and local codes.

• Component approvals and performance ratings are based on

the use of Thermon specifi ed parts only. User supplied power
connection fi ttings must be listed or certifi ed for intended use.

• De-energize all power sources before opening enclosure.

• Keep ends of heating cable and kit components dry before and

during installation.

• Individuals installing these products are responsible for

complying with all applicable safety and health guidelines.
Proper personal protective equipment, or PPE, should be
utilized during installation. Contact Thermon if you have any
additional questions.

Dimensions . . .

C

A

inch (mm)

B

inch (mm)

C

inch (mm)

FAK-5

11-7/8” (302 mm)

9-1/8” (232 mm)

3-1/2” (89 mm)

FAK-5L

15-5/8” (397 mm)

10-1/2” (267 mm)

4” (102 mm)

B