Terminator, Zp-mi-wp, Installation procedures – Thermon ZP-MI-WP Terminator User Manual

Page 2

background image

2

Item

Quantity

Description

1

1

Expediter Assembly

Support Cap with O-Ring

Threaded Grommet Compressor

Grommet

Wall Mount Support Base with O-Ring

2

1

Junction Box Lid

3

1

Junction Box Base with O-Ring

4

1

Wall Mount Bracket

5

3

M5 Screws

6

3

Lock Washers

7

1

Terminal Block with DIN Rail

8

1

Junction Box Lid Cord

9

1

Nut

10

1

Power Gland

11

1

Blind Plug

12

2

Wire Pins (per MI Cable Cold Lead)

13

1-2

Banding (Optional, see Steps 1a or 1c)

14

1

XP-1 Bracket (Optional, see Step 1c)

Kit Contents . . .

2

4

3

4

1

5

6

7

8

9

10

11

B-type Tanding (order separately)
B-4: for pipes up to 4"
B-10: for pipes up to 10"
B-21: for pipes up to 21"

13

XP-1-140X80 Stainless Steel

Mounting Bracket
(order separately)

14

Terminator

TM

ZP-MI-WP

INSTALLATION PROCEDURES

Wire Pins (per MI cable cold lead,order separately)

12

Certifications/Approvals . . .

1725 II 2 GD Ex eb IIC T4-T6, Ex tb IIIC T135°C-T85°C FM 10ATEX0058X

IP66 -60°C ≤ Ta ≤ +55°C
Ordinary & Hazardous Locations

IECEx FMG 10.0022X Ex eb IIC T4-T6, Ex tb IIIC T135°C-T85°C

Warnings . . .
• Due to the risk of electrical shock, arcing and fire caused by

product damage or improper usage, installation or mainte-

nance, a ground-fault protection device is required.

• Installation must comply with Thermon requirements and be

installed in accordance with the regulations as per the norm

EN IEC 60079-14 for hazardous areas (where applicable), or

any other applicable national and local codes.

• Install correct heating cable lengths indicated in the design.

Any deviations from these lengths will result in a change in

outputs.

• Component approvals and performance ratings are based

on the use of Thermon specified parts only.

• De-energize all power sources before opening enclosure.
• Keep ends of heating cable and kit components dry before

and during installation.

• Minimum bending radius of heating cable is 6 times the cable

outer diameter.

Tools Required . . .

Terminator-LN-Tool
(order separately)

3 mm
8 mm

2.5 mm

2

6.0 mm

2

26 mm
28 mm

29 mm
33 mm