1. Install heating cable in accordance with Illustrations
F and G below. Secure heating cable to piping using
stainless steel tie wire or banding.
2. Additional cable is required to provide extra heat at
valves, pumps and miscellaneous equipment to offset
the increased heat loss associated with these items.
Refer to Table 2 for estimated cable requirements for
installation on typical valves and pumps.
3. Install heating cable on valves and pumps utilizing a
looping technique (this allows the valve or pump to be
removed if required). Do not cross cable.
4. Minimum bend radius is 6X cable O.D. Do not exceed
bend radius when completing installation.
5. In potentially explosive areas, it is recommended to
secure MIQ cable with stainless steel banding at all
fl anges, valves or any other irregular shaped equipment.
Table 2: Valve and Pump Allowances
Illustration G: Typical Pump Detail . . .
Heating Cable Serpentined on Valve
Heating Cable Serpentined on Pump
MIQ Heating
Cable
MIQ
Heating Cable
Stainless Steel Tie
Wire or Banding
Notes. . .
1. The valve allowance given is the total amount of additional cable to be installed on
the valve. If multiple tracers are used, total valve allowance may be divided among
the individual tracers. The total valve allowance may be alternated among tracers for
multiple valves in a heat trace circuit.
2. Allowances are for 150 pound valves. More cable is required for higher rated
valves.
3. Refer to heat trace isometric drawing for project specifi c allowances.
Illustration F: Typical Valve Detail . . .
Stainless Steel Tie
Wire or Banding
Pipe Size
mm
Valve Type
Pump Type
Screwed
or Welded
m
Flanged
m
Butterfl y
m
Screwed
m
Flanged
m
12
.15
.30
0
.30
.61
19
.23
.46
0
.46
.91
25
.30
.61
.30
.61
1.22
32
.46
.61
.30
.91
1.37
40
.46
.76
.46
.91
1.52
50
.61
.76
.61
1.22
1.68
80
.76
1.07
.76
1.52
2.13
100
1.22
1.52
.91
2.44
3.05
150
2.13
2.44
1.07
4.27
4.88
200
2.90
3.35
1.22
5.79
6.71
250
3.81
4.27
1.22
7.62
8.53
300
4.57
5.03
1.52
9.14
10.06
350
5.49
5.94
1.68
10.97
11.89
400
6.55
7.01
1.83
13.11
14.02
450
7.77
8.23
1.98
15.54
16.46
500
8.69
9.14
2.13
17.37
18.29
600
10.36
10.97
2.44
20.73
21.95
750
12.19
12.80
3.05
24.38
25.60
NOTE:
Individual MIQ cable set
recommended for pumps.
5