SECTION 4 - FAULT FINDING
Problem:
Nothing happens when the unit is powered-up.
Cause / Remedy:
One of the fuses could be blown - check and replace if
necessary (refer to specifications for values). If the fuse blows
again, contact the agent where the unit was purchased.
Problem:
The temperature display is fluctuating.
Cause / Remedy:
One of the sensor connections may be loose. Tighten
connections and re-route cables if necessary.
Problem:
Unable to set any of the parameters: Keypad will not operate.
Cause / Remedy:
The keypad Lock is on - see ‘Keypad Lock’ section 3.5.2.
Problem:
One of the sensors is reading “F”.
Cause / Remedy:
One of the sensors is either faulty or not properly connected or
is reading a temperature above 100°C. The sensor, which is
causing the problem, will show “F” on the display when
selected. Check that all connections / couplers are secure. If
the fault persists, replace the sensor.
Problem:
The “T” light is flashing even when the keypad lock is engaged.
Cause/Remedy:
This is not a fault. This is an indication that the temperature of
the collector is below the anti-frost set point (-15°C), and the
pump should be on.