CHARACTERISTICS WITH REGARDS TO SAFETY

Equipment conforms to the following directives and norms.

73/23/EEC Low voltage.

89/336/EEC Electromagnetic compatibility

94/9/EC (ATEX) Equipment & protective systems intended for use in potentially explosive

atmospheres

EN 50014 Electrical apparatus for potentially explosive atmospheres. General

requirements.

EN 50018 Electrical apparatus for potentially explosive atmospheres. Flameproof

enclosures “d”.

EN 50281-1-1 Electrical apparatus for use in the presence of combustible dust. Part 1-1

electrical apparatus protected by enclosures.

This instrument, since it belongs to Group II, is destinated to be used in areas where there is a
hazard of explosive atmospheres forming, except for mining installations.
Since it is category 2GD it can be used in ambients where there is a probability of formation of
explosive atmospheres due to gases, vapours, mists or powder in suspension.

IMPORTANT

The respective national regulations, as well as the general engineering rules that apply to the
installation and operation of apparatus in explosive atmospheres must be observed .

The end user is responsible for the safe use of this equipment.

Modification or reparation of the flameproof housing is not permitted.

The opening of the housing always shall be done without voltage. The housing is considered
to be closed when the lid is completely screwed down and the grub screw in its locking
position.

Only approved EExd IIC cable glands with the same thread as the housing should be used.

The flameproof seals of the housing should kept greased to avoid corrosion, water ingress
and seizing. Clean rests of grease and corrosion, do not use sharp objects that can damage
the surface of the seal, and grease using a chemically and thermally stable grease with a
drip point > 200ºC.

In applications with combustible dust, make sure that layers of more than 5 mm do not form.

For the models that have non-metallic parts, the occurrence of electrostatic risks, must be
taken into account. They should not be used in locations where formation of electrostatic
charge can occur. During maintenance, these parts should always be cleaned using a damp
cloth.


NOTE: The LT/LTL series level, to which this limit switch belongs, can be installed in a tank in
which the inside is considered to be zone 0, because the part that is inside the tank is a simple
Non electrical equipment without ignition sources.

!