Introduction, Specifications, Instrument terminals – Super Systems 9015 Series User Manual
Page 3: Introduction specifications instrument terminals
Super Systems Inc. Page 3 of 11
Series 9015 Operations Manual
Introduction
The 9015 Events Module and Relay Extension is designed to expand the event and relay
capabilities of a 92XX controller. The 9015 is based on the 9010 eSPP with events
hardware. This provides 8 output event relays and 4 event inputs (dry contact). A
second 9015 can be connected to the first 9015 to seamlessly provide 16 outputs and 8
inputs.
Additional features have been added to the 9015 to provide digital I/O, combination logic,
and counters to the Video Recorder.
Specifications
The following specifications are applicable to the 9015 instrument.
Item
Specification
Power Input
24VDC +/- 20% at 300 Ma
Relay Contacts
24VDC at 200 mA max
Input
Dry contact or open collector sinking common to
24VDC supply. Protected from overvoltage.
Ethernet
10-base T Modbus TCP (factory default IP
192.168.0.222)
RS-232
Modbus, 8N1, baud rates from 1200 to 115200
(factory default 19200)
RS-485 Host
Modbus, 8N1, baud rates from 1200 to 115200
(factory default 19200)
RS-485 Slave 1
Modbus, 8N1, baud rates from 1200 to 115200
(factory default 19200)
RS-485 Slave 2
Modbus, 8N1, baud rates from 1200 to 115200
(factory default 19200)
RS-485 Modbus
host address
1 to 249 (factory default 222)
RS-485 Slave 1
setup
Slave instrument 1 is forced to SSI 8-8 address 222
Table 1 - 9015 Instrument Specifications
Instrument Terminals
Correct use of instrument terminals is crucial for use of the 9015 instrument. The 32