Title: Southern States
– CSV
Vertical Interrupter Style Circuit Switcher
Product Specification Guide
Page 4 of 9
Publication No.: PSG-806-CSV 06012011
Ratings
Maximum kV Rating
245
Interrupter/Blade BIL (kV)
900
Continuous Current
1200 A
Primary fault Interrupting
20 kA
Secondary Thru-Fault
4 kA
Interrupting Time
6 cycles
Power Frequency
60 Hz
Short-Time Withstand
40 kA (3 sec)
Peak Withstand
104 kA
Short Circuit Making
40 kA
Insulator Design
Porcelain
Ambient Temperature
-30° C to + 50° C
3.02.02 Additional
1. Rated Interrupting Time: 5 cycles for 27 kV through 72.5 kV
units, 3 cycles for 38 kV through
170 kV units, 6 cycles for 245 kV
2. Rated Duty Cycle:
O-0.3 sec-CO-15 sec-CO
3.02.03 Source Supply Voltage
Purchaser will supply the following sources for the motor, auxiliary, and
control circuits:
1. Motor Voltage
48 VDC, 125 VDC, 250 VDC, 120
VAC, or 240 VAC
2. Auxiliary Voltage
120 / 240 VAC, 60 Hz, 1
3. Control Voltage
48 VDC, 125 VDC, 250 VDC, 120
VAC, or 240 VAC
3.03 Interrupter
The circuit switcher shall use SF
6
single gap puffer interrupters. Arc assist type
interrupters are not acceptable. Each interrupter shall be provided with an
overpressure relief device and shall be field refillable. Hermetically sealed
interrupters are not acceptable due to the inherent dangers to purchaser’s
personnel associated with handling fully pressurized SF
6
devices during
installation and also due to potential hazards encountered during transportation
and offloading.
3.04 Insulators
The support insulators and the interrupter insulators shall be ANSI 70 gray in
color and either porcelain or composite in construction.