3.02 Ratings
3.02.01 Electrical
Maximum kV Rating
27
38
38
48.3
72.5
38
48.3
72.5
BIL (kV)
150
200
200
250
350
200
250
350
Continuous Current
Primary Fault
Interrupting
Secondary Thru-Fault
Interrupting
Interrupting Time
Power Frequency
Short-Time Withstand
Peak Withstand
Short-Circuit Making
Insulator Design
Ambient Temperature
Range
-40º C to +50º C
1200 A
25 kA
5 cycles
-40º C to +50º C standard
(-50º C to +50º C optional)
Porcelain
Composite
Porcelain
3 cycles
40 kA
1200 A, 1600 A, 2000 A, 2500 A
4
Ratings
62.5 kA
25 kA
50/60 Hz
1200 A & 1600 A
25 kA
5 cycles
50/60 Hz
25 kA (3 sec)
4
-30º C to +50º C
40 kA
104 kA
40 kA (3 sec)
4
60 Hz
40 kA (3 sec)
104 kA
40 kA (3 sec)
Maximum kV Rating
48.3
72.5
123
145
170
Interrupter/Blade BIL (kV)
250
350
550
650
750
Continuous Current
Primary Fault Interrupting
Secondary Thru-Fault
Interrupting
Interrupting Time
Power Frequency
Short-Time Withstand
Peak Withstand
Short-Circuit Making
Insulator Design
Ambient Temperature
Range
*
4000 A rating is only available thru 145 kV.
40 kA (3 sec), 63 kA (1 sec)
164 kA
63 kA
Porcelain
-40º C to +50º C standard
(-50
o
C to +50
o
C optional)
Ratings
1200 A,1600 A, 2000 A, 3000 A, 4000 A*
25 kA, 31.5 kA, 40 kA
4
3 cycles
60 Hz