N0922L, N1322L, F1222L, F1522L

D Series Remote Low Side User Manual

October 2014

Page 9

Refrigeration

BTUH Capacity Requirements

Model

BTUH

N0922L, F1222L

5,000

N1322L, F1522L

7,200

Condensing Units

Model Use Condensing Unit

N0922L or F1222L

NME954-RHS-A/C

N1322L or F1522L

None - rack only

Remote low side models require connection to a

dedicated condensing unit or a rack system.

Recommended Tubing from Head to Condensing Unit

• Suction Line: 5/8" OD

• Liquid Line: 3/8" OD

Distance limits:

• Maximum distance between dedicated condensing

unit and head: 75 feet.

• Condensing Unit Elevation over Ice Making

Section: 35 feet.

Note: Elevations greater than 20 feet require

installation of a suction line trap at the 10 foot mark.

Ice Making Section

• Elevation over Condensing Unit: 15 feet.

Line Routing:

• Allowed: One rise after a drop.

• Allowed: One drop after a rise.

• Not Allowed: More than one rise after a drop

• Not Allowed: More than one drop after a rise

Roof Attachment

Install and attach the remote condensing unit to the

roof of the building, using the methods and practices

of construction that conform to the local building

codes, including having a roofing contractor secure

the condenser to the roof.

Refrigeration Installation:

Connections

The liquid and suction fittings on the back of the

cabinet are stubs. The liquid line size is 3/8" OD. The

suction line size is 5/8" OD.

1. Recover holding charge

2. Cut the stubs off.

3. Braze line set tubing to each fitting. Sweep with

dry nitrogen while brazing.

4. Dedicated condensing unit: Evacuate complete

system to 50 microns.

5. Open the ball valves.

Rack: The skills of a refrigeration technician are

required to connect the ice machine to the building’s

refrigeration system.

Notes:

• R-404A models: 1.5 ounces of R-404A refrigerant

is in the system as a holding charge.

• Be sure the liquid connection is NOT in series with

another liquid line valve.

• Local Codes must be observed.

Dedicated condensing unit: Add refrigerant charge.

Recommended starting field charge:

• N0922L or F1222L: 8 lb R-404A

• N1322L of F1522L: n/a - rack only