5 commissioning, Commissioning – REMKO Safety assembly User Manual

Page 9

background image

NOTICE!

Carry out the installation such that the safety

assembly is located above the level of the heat

generator.

A

B

G

D

E

F

C

H

I

Fig. 2: Installation schematic

A:

Outdoor unit

B:

WKF series indoor unit

C:

Safety assembly

D:

Cold water

E:

Circulation

F:

Hot water

G:

Floor heating cycle

H:

Supply line

I:

Return line

5

Commissioning

With the initial commissioning of the heating

system, the heat pump is filled until the static pres-

sure of the system is reached. The heat pump is

now brought to the max. heating temperature

whereby care should be taken to ensure that the

pressure increase does not exceed 2 bar. If this

does however exceed 2 bar then the expansion

vessel has been incorrectly selected.

The trigger pressure and rating of the diaphragm

safety valve can be found on the safety placard on

the red hand knob.

9