Series
SLE 40
SLE 60
SLE 80
Daily dehumidification capacity at 30°C and 80%
relative humidity
Litre/day
50.4
70.8
100.8
Daily dehumidification capacity at 30°C and 60%
relative humidity
Litre/day
32.2
43.2
64.0
Operating temperature range
°C
10 to 36
Humidity operating range
% rel. humidity
40 to 100
Air capacity
m
3
/h
250
500
750
Power supply
V/Hz
230/1~/50
Max. power consumption
kW
0.72
1.05
1.65
Max. rated power consumption
A
2.8
4.3
7.2
Refrigerant
R407C
Refrigerant quantity
kg
0.6
0.95
1.6
Sound pressure level L
pA
1m
1)
dB (A)
47
49
51
Depth
mm
315
315
315
Width
mm
950
1260
1800
Height
mm
800
800
800
Weight
kg
60
74
101
EDP No.
615400
615600
615800
Technical Data
1) Noise measurement DIN 45635 - 13 - Category 3
We reserve the right to make dimensional and design changes in the interest of technical advances.
19