Trouble Shooting

The units were manufactured us-
ing the latest production methods
and tested repeatedly for perfect
function. If faults should still occur,
the unit must be checked against
the following list.

The unit does not start.

Check the operating switch set-

ting. The green pilot light must
illuminate

Check the supply connection

and local system fuse 230V/1~/
50Hz

Check the mains plug and mains

cable for damage

Check the level in the conden-

sate container and the container
for correct seating. (not for AMT
110-E)

Check the hygrostat setting (ac-

cessory).
The setting must be lower
than the relative humidity in
the room in which the unit is
installed

Check the adapter plug of the

hygrostat for damage and cor-
rect seating

The red (Fault) pilot light il-
luminates

The cooling circuit is overloaded

or overheated

Before restarting the unit, the

cause of the fault must first be
located.
To be noted is that the unit re-
starts automatically after cooling
down

The unit operates, but no
condensate forms

Check the room temperature.

The operating range of the unit
is between 3°C and 32°C

Check the humidity, min. 40%

RH necessary

Check the dust filter for clog-

ging and clean or replace as
necessary

Check the evaporator and

condenser fins for clogging and
clean if necessary

Check the evaporator for pos-

sible icing/frost formation.
If this is the case, the automatic
defrost function and tempera-
ture sensor must be checked

If the unit does not operate cor-

rectly despite the checks carried
out, an authorised specialist
company should be notified

Cleaning the units

For cleaning the interior of the unit
and to gain access to the electri-
cal components, it is necessary to
open the unit housing.

1. Remove the two fixing screws

[B].

2. Lift the housing part and hang

out the front tabs.

3. Clean the condenser fins either

by blowing out, suction or with
a soft brush.

4. Clean the evaporator fins, e.g.

with a luke-warm soap solution

or similar.

5. Do not use a direct water jet.

6. Rinse with clean water to re-

move adhering soap residues.

7. Clean the inner surfaces of the

unit and fan impeller.

8. Clean the condensate trap and

connection.

9. After cleaning, the unit must be

dried.

Pay special attention to the

electrical components!

10. Refit all removed parts correctly

in reverse order.

11. Carry out a functional check

and safety test on the unit.

NOTE

Particular care must be taken

when cleaning the exchanger

as the fine aluminium fins bend
very easily.

CAUTION

Only specially authorised
firms may carry out work on
the refrigeration system and
electrical equipment.

NOTE

Adjustment and maintenance
tasks may be performed only
by authorised expert
personnel!

CAUTION

After completing all work on
the units, an electrical safety
test must be carried out in
accordance with VDE 0701.

B

B

14

REMKO AMT