Action in the Case of Faults

- Unit does not start


- Unit switches off during operation (fault-indicating lamp in
automatic burner is lit up)


- Fan runs, but gas supply is blocked or there is no ignition


- Gas supply is interrupted or flame goes out


- Unit consumes too much combustible


- Unit cannot be switched off


- Heating capacity is reduced with continuous operation


- Heating capacity cannot be regulated

1 – 2 – 3 – 4 – 5 – 7 – 10 – 13 – 17 – 18


2 – 6 – 7 – 8 – 9 – 10 – 13 – 14 – 17


7 – 12 – 13 – 14


6 – 7 – 8 – 9 – 10 – 13 – 14 – 17 – 18


13


5 – 15


14


11

Cause:

Faults:

Cause:

Remedy:

1. Unit has no electrical connection

– Insert plug into appropriate socket (230V/1-50Hz)

2.

Fan motor is overloaded
(air supply fan runs irregularly or is blocked)

– Control motor, fan wing and carrier coupling and replace,

when necessary

3. Value set on room thermostat is too low

– Set value must be higher than that of actual room temperature

4. No bridge plug in the room thermostat socket

– Connect bridge plug with the thermostat socket

5. Faulty operating switch

– Cut off gas supply, remove plug from mains socket and replace

operating switch

6. No polarity

– Turn mains plug by 180° (check polarity)

7. No gas pressure on solenoid valve

– Control whether gas is supplied to the unit
– Control contents of gas bottles
– Check whether gas hose is damaged
– Unlock or replace hose security device (protection against breaka-

ge)

8. Ionisation and/or initiating electrode incorrectly set

– Set according to instructions; check porcelain insulation of electro-

des

9. Suction protective lattice of air supply fan is dirty

– Clean suction protective lattice

10.

- switching-off by safety temperature limiter (STB)
- Mains plug disconnected from mains supply before the
post-cooling time has lapsed (only PGT 100)

– Control suction and exhaust protective lattice (clean, when neces-

sary)

– Control whether there is sufficient fresh air supply
– Unlock STB (STB – Reset)

11. Gas regulation faulty or dirty

– Replace or clean gas regulation

12. Ignition does not work

– Operating switch into “I” position (heating operation)
– Check whether ignition cable is damaged
– Check electrode setting, check cycle igniter

13.

Pressure regulator is either faulty or a wrong pressure regulator
has been installed, or the hose break protection (SBS) has lok-
ked

– Install original pressure controller
– Unlock or replace hose security device (protection against breaka-

ge)

14.

Gas bottle is iced due to low temperatures and high consumed
gas rate

– Replace gas bottle and connect 2 or 3 bottles with the multi-bottle

set, EDP no. 1014050

15. Solenoid valve does not close

– Cut off gas supply
– Let flame burn out
– Put operating switch into “0” position and remove mains plug from

mains socket

– Replace solenoid valve

16. Untight gas connection

– Detect leakage by means of foaming agents and eliminate it

17. Fault-indicating lamp in the automatic burner relay is lit up

– Unlock automatic burner relay by pressing the fault button

18. Faulty automatic burner relay

– Replace faulty automatic burner relay