beautypg.com

Troubleshooting, Technical data, Service and guarantee – REMKO ELT 3-2 User Manual

Page 6

background image

6

Troubleshooting

Unit (fan) does not start:

1. Check main fuse

2. Check connecting cable with plug

3. Check operating switch

4. Check slight drifting of fan (motor)

Unit does not heat

1. Check operating switch

2. Check auxiliary relay / contactor (ELT 10-6 / ELT 18-9).

3. Check function of temperature limiter resp. check

capillary tubing (if damaged)

4. Check if thermostat plug resp. bridge circuit plug is

coupled

5. Check thermostat-operation: thermostat must be set

higher than the room temperature

Series

ELT 3-2

ELT 10-6

ELT 18-9

Nominal heat output

kW

3,2

10,5

18

Switchable heat output

kW

1 x 3,2

3 x 3,5

3 x 6

Air output

m³/h

350

750

1000

Electrical connection

V

230/1~

400/3~

400/3~

Frequency

Hz

50

50

50

Rated current

A

13,9

14,9

27,5

Power consumption max.

kW

3,25

10,65

18,2

Fuse protection (required)

A (inert)

16

16

32

Sound pressure level L

pA

1m

1)

dB (A)

46

53

57

Dimensions

Length

mm

400

675

740

Width

mm

200

300

335

Height

mm

335

455

500

Weight

kg

6,8

20,0

27,4

1) noise measuring DIN 45635 - 01 - KL 3

Technical Data

Should the unit still not be working despite these checks,
please contact an authorised service centre.

Prior to starting any work make sure to pull the
mains

plug

out

of

the

mains

socket!

Setting and maintenance is to be carried out
only by authorised experts!

Correct usage

The units are to be used only for heating and ventilation
purpose in industrial or commercial application because
of their construction and equipment.

If specification of the manufacturer or legal regulations,
are not followed or if unauthorised changes are made
on the unit, the manufacturer is not liable for resulting
damages.

An operation/use other than that indicated in these
instructions is prohibited!
In the case of non-observation we will not be held
responsible and our guarantee will become void.

Service and Guarantee


Any claims under guarantee regarding materials can be
accepted only when the orderer or his customer has
filled in completely the “guarantee certificate” which is
enclosed with every REMKO-heater and has returned it
to REMKO GmbH & Co. KG in due time after the unit’s
sale and commissioning.

The units are factory tested on faultless function. If any
failure occurs though which cannot be eliminated by the
operating person, please contact your dealer or contact
person.

This manual is related to the following products: