Troubleshooting
Unit (fan) does not start:
1. Check main fuse
2. Check connecting cable with plug
3. Check operating switch
4. Check slight drifting of fan (motor)
Unit does not heat
1. Check operating switch
2. Check auxiliary relay / contactor (ELT 10-6 / ELT 18-9).
3. Check function of temperature limiter resp. check
capillary tubing (if damaged)
4. Check if thermostat plug resp. bridge circuit plug is
coupled
5. Check thermostat-operation: thermostat must be set
higher than the room temperature
Series
ELT 3-2
ELT 10-6
ELT 18-9
Nominal heat output
kW
3,2
10,5
18
Switchable heat output
kW
1 x 3,2
3 x 3,5
3 x 6
Air output
m³/h
350
750
1000
Electrical connection
V
230/1~
400/3~
400/3~
Frequency
Hz
50
50
50
Rated current
A
13,9
14,9
27,5
Power consumption max.
kW
3,25
10,65
18,2
Fuse protection (required)
A (inert)
16
16
32
Sound pressure level L
pA
1m
1)
dB (A)
46
53
57
Dimensions
Length
mm
400
675
740
Width
mm
200
300
335
Height
mm
335
455
500
Weight
kg
6,8
20,0
27,4
1) noise measuring DIN 45635 - 01 - KL 3
Technical Data
Should the unit still not be working despite these checks,
please contact an authorised service centre.
Prior to starting any work make sure to pull the
mains
plug
out
of
the
mains
socket!
Setting and maintenance is to be carried out
only by authorised experts!
Correct usage
The units are to be used only for heating and ventilation
purpose in industrial or commercial application because
of their construction and equipment.
If specification of the manufacturer or legal regulations,
are not followed or if unauthorised changes are made
on the unit, the manufacturer is not liable for resulting
damages.
An operation/use other than that indicated in these
instructions is prohibited!
In the case of non-observation we will not be held
responsible and our guarantee will become void.
Service and Guarantee
Any claims under guarantee regarding materials can be
accepted only when the orderer or his customer has
filled in completely the “guarantee certificate” which is
enclosed with every REMKO-heater and has returned it
to REMKO GmbH & Co. KG in due time after the unit’s
sale and commissioning.
The units are factory tested on faultless function. If any
failure occurs though which cannot be eliminated by the
operating person, please contact your dealer or contact
person.