beautypg.com

Technical data – REMKO RKS 327 H User Manual

Page 13

background image

13

RKS 327 H

RKS 335 H

RKS 350 H

RKS 371 H

Cooling capacity *

W

2600

3500

5000

7100

Heating capacity **

W

2900

3870

6040

7620

Operating range (size of room approx. )

80

110

160

230

Refrigerant

R 407 C

Connection injector line

inches (mm)

1/4 (6.35)

3/8 (9.52)

Connection suction line

inches (mm)

3/8 (9.52)

5/8 (16.0)

Length of line/ height difference, max.

m

10 / 5

15 / 8

Additional amount to add for 5 m or longer

g/m

30

Electrical connection

V/Hz/Ph

230 / 50 / 1~, N, PE

Power consumption cooling *

W

1020

1200

2190

3000

Power consumption heating **

W

1030

1180

2190

3100

Power consumption max.

W

1450

1700

3100

4500

Current consumption cooling

A

5.0

5.5

8.5

13.5

Current consumption heating

A

4.8

5.4

10.3

14.0

Supplied fuse protection (recommended)

A

16

16

20

25

Indoor unit

RKS 327 H-IT RKS 335 H-IT RKS 350 H-IT

RKS 371 H-IT

Operating range cooling inside/outside temperature

°C

17 to 30 / -7 to 43

Operating range heating inside/outside temperature

°C

17 to 30 / -7 to 24

Dehumidification capacity max.

l/h

1.00

1.30

1.70

2.22

Air performance level 1/2/3

m³/h

320 / 360 / 410 400 / 480 / 540 670 / 740 / 800 750 / 880 / 1050

Fan speeds

-

3

Fan capacity

W

30

45

52 55

Type of protection

IP

X0

Sound pressure level 1/2/3 ***

dB(A)

33 / 35 / 39

36 / 38 / 40

42 / 43 / 44

42 / 44 / 47

Dimensions H / W / D

mm

265 / 785 / 150 300 / 900 / 175 315 / 1025 / 210 320 / 1180 / 200

Weight kg

10

10

14

20

Outdoor part

RKS 327 H-AT RKS 335 H-AT RKS 350 H-AT

RKS 371 H-AT

Operating range

°C

- 7 to + 43

Refrigerant quantity

kg

0.83

0.73

1.85

2.6

Type of protection

IP

24

Air performance max.

m³/h

1500

1600 2200 2500

Sound pressure level, max. *** dB(A)

53

53

54

56

dimensions H / W / D

mm

540 / 780 / 245 540 / 780 / 245 695 / 845 / 330

860 / 900 / 350

Weight kg

36

36

55

70

Manufacturing number

374....

379....

380....

381....

Ref. No.

1613330

1613335

1613350

1613371

1/2 (12.7)

Technical Data

* Capacities are based on ISO R 859A; room temperature of TK 27 °C/FK 19 °C - outside temperature 35 °C
** Capacities are based on a room temperature of TK 20 °C - outside temperature 7 °C
*** Noise measurement DIN 45635 - 01 - KL3
**** At a room temperature of 20 ºC.

10 ºC TK

9 ºC FK

7 ºC TK
6 ºC FK

4 ºC TK
3 ºC FK

0 ºC TK

-1 ºC FK

-4 ºC TK
-6 ºC FK

-7 ºC TK
-8 ºC FK

RKS 327 H Heating capacity W

****

3,225

2,900

2,490

2,095

1,745

1,605

Electrical capacity W

****

1,195

1,130

1,035

995

965

915

RKS 335 H Heating capacity W

****

3,995

3,870

3,190

2,725

2,235

2,005

Electrical capacity W

****

1,300

1,180

1,135

1,075

1,015

970

RKS 350 H Heating capacity W

****

6,950

6,040

5,790

4,935

4,000

3,545

Electrical capacity W

****

2,385

2,190

2,105

1,970

1,825

1,790

RKS 371 H Heating capacity W

****

8,685 7,620 7,015 4,250 3,960 3,485

Electrical capacity W

****

3,555 3,100 2,815 2,480 2,345 2,105

Outdoor temperatures

Heating capacity

This manual is related to the following products: