11. Technical Specification
Specifications for 120VVAC /277VAC
Capacity (W)
Description
500
750
1000
1250
1500
2100
Input
Voltage
Single Phase 120Vac or 277Vac
Voltage Range
120Vac ±10% or or 277Vac
Frequency
60Hz +/- 4Hz
Output
Voltage (on battery)
Single Phase 120Vac or 277Vac
Voltage Range
120Vac ±2% or 277Vac
Frequency (on battery)
60 Hz +/-0.5%
Transfer Time
0 ms
Overload Recovery
Auto transfer to UPS
High Efficiency mode (AC to AC)
> 95 %
UPS Design Technology
On-Line / Fully digitized microprocessor controlled
Output Wave Form
Sine wave
Harmonic distortion
< 3% of T.H.D. at linear load
Protection and
Filtering
Overload Protection
125% for 1 minutes and 150% for 10 seconds
Short Circuit Protection
Circuit breaker
System/Display/
Warning
Visual Display
(LED model)
UPS on(green), line-mode(green),
battery mode(yellow), bypass(yellow), fault(red)
Visual Display
(LCD model)
Input / output voltage, input / output frequency,
on-line mode, back up mode, battery capacity, load
level
Audible Alarm
(Battery back-up)
Beep every 5 sec
UPS Fault
Continuous beeping sound and LCD display
Communication
RS-232 Serial Port and USB
Battery
90 min. UL924
(Sealed, maintenance
free lead acid battery
8X26 A/H 8X35 A/H
8X35 A/H
8X50 A/H
8X65 A/H
8X65A/H
Dimensions
(Inches) Width x Height x Depth
23.5 X 34.25 X 18.25
Environmental
Operating Temperature
0 - 40ºC / 32 ~ 104ºF
Storage Temperature
-20 ~ 50ºC / -4 ~ 122ºF
Audible Noise
(1 meter from surface)
< 40 dBA
Relative Humidity
0 ~ 95% humidity, non-condensing
Note: Due to continuous improvement, specifications are subject to change without prior notice.