OnLine Power Power Wave 1 User Manual
Page 20

6005-085 Rev B
19
8.
Bypass Range Set Menu:
a. To protect the load, the function of bypass auto-transfer is activated only when the
AC main voltage is within the range of LO (low) and HI (high). In this screen, press
the ON/OFF Control key to enter the following steps for LO/HI voltage setting:
b. The cursor () will appear to indicate the selected item. Press the ON/OFF Control
key to find the LO or HI range display.
c. Use the Up or Down key to adjust the voltage (1V for every press) to the desired
setting.
d. Once the value is confirmed, press the ON/OFF Control key again to save the data: