20
11. Technical Specification
Specifications for 120V/277V
Capacity (W)
200W
300W
490W
Voltage
Single Phase 120Vac or 277V
Voltage Range
120Vac ±10% or 277V
Frequency
50Hz or 60Hz +/- 4Hz
Input
Power Factor
> 95%
Voltage (on battery)
Single Phase 120Vac or 277V
Voltage Range
120Vac ±2% or 277V
Frequency (on battery)
50 / 60 Hz +/-0.5%
Transfer Time
0 ms
Overload Recovery
Auto transfer to UPS
High Efficiency mode (AC to AC) > 95 %
Output
UPS Design Technology
On-Line / Fully digitized microprocessor controlled
Surge Protection
120V (IEEE C62.41) / 230V (IEEEC61000-4-5 level 3)
Overload Protection
125% for 1 minutes and 150% for 10 seconds
Protection and Filtering
Short Circuit Protection
Circuit breaker
Visual Display
(LED model)
UPS on(green), line-mode(green),
battery mode(yellow), bypass(yellow), fault(red)
Visual Display
(LCD model)
Input / output voltage, input / output frequency,
on-line mode, back up mode, battery capacity, load level
Audible Alarm
Beep every 5 sec
UPS Fault
Continuous beeping sound and LCD display
System/Display/ Warning
Communication
RS-232 Serial Port and USB
Battery
90 min.
2X35 A/H
2X50 A/H
2X50 A/H
Dimensions
Inches (width x Height x depth)
24 x 17 x 9.5
Note: Due to continuous improvement specifications are subject to change without prior notice