beautypg.com

Integer format output network variables – ONICON System-10 LonWorks User Manual

Page 19

background image

11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]
System-10-LON Network Interface Installation Guide 05/14 - 0654-5 / 16751

Page

A-3

INTEGER FORMAT OUTPUT NETWORK VARIABLES

Integer format output variables are limited to 2 bytes of data. For this reason, the maximum number that
can be transmitted in this format is 65,535. Values for both rate and total data from the Btu meter will often
exceed this limit. For this reason, energy rate data is scaled and energy totals are transmitted in segments
using multiple variables. This is explained in detail below.

Volume and Energy Rate Variables

The integer output network variables for volume and energy rate are described in the table below. Column
1 contains a brief description of the network variables. Column 2 contains the network variable names.
Column 3 contains the Lon SNVTs used for each variable. Column 4 contains the engineering units and
column 5, the valid range for each variable. Please note that while the floating point variable for energy
rate is transmitted in Watts, the integer network variable is transmitted in kW to ensure that the maximum
rate never exceeds the register capacity.

Integer Output Network Variables

Description

Variable Name

SNVT Name

Engineering Units

Valid Range

Flow (volume) rate

nvoVolRateLi

SNVT_flow

Liters/Sec

0 to 65535

Mode status indicator

nvoModeStatus

SNVT_char_ascii

Supply temperature

nvoSupplyTempi

SNVT_temp_p

° C

-17.778 to 260.0

Return temperature

nvoReturnTempi

SNVT_temp_p

° C

-17.778 to 260.0

Delta temperature

nvoDeltaTempi

SNVT_temp_diff_p

° C

-327.68 to 327.66

Energy rate

nvoEnrRateKWi

SNVT_power_kilo

KWatts

0 to 65535

Volume and Energy Total Variables

The integer output network variables for volume and energy total are described in the table below. Column
1 contains a brief description of the network variables. Column 2 contains the network variable names.
Column 3 contains the Lon SNVTs used for each variable. Column 4 contains the engineering units and
column 5, the valid range for each variable.

Please note that while the floating point variable for volume total is transmitted in liters, the integer
network variable for volume total is transmitted in kLiters. This is done to increase the maximum total
that can be transmitted via the integer variable. Total(s) must be reset before the accumulated value
exceeds 6553.5 kliters using nviResetVol1a and/or nviResetVol2a. If this is not done, nvoVol1KLi and/or
nvoVol2KLi will over range and continue to indicate 6,553.5 kliters (1,731,252 gallons) until the
System-10’s internal total rolls over to zero.

A separate integer SNVT is also available to transmit flow totals in liters. This variable is only used in
special small pipe applications as the maximum total it can accumulate is only 65,535 liters (17,312
gallons) before it must be reset.

Energy totals are handled in a slightly different way. The floating point variable for energy total is
transmitted in Btu but the integer network variable for energy total is MBtu. This total will over range at
65,535 MBtu. The internal total stored in the Btu meter will not roll over until it exceeds 99,999.99 MBtu.