1.7.6 Rollover of Totals

The totals stored in the flow Btu meter memory will roll over to zero when the maximum

count is exceeded. When this occurs, the network totals will also roll over to zero. The

point at which the rollover occurs is a function of the displayed engineering units and

multipliers programmed into the System-10.

The examples below show the rollover point in the engineering units transmitted by the

network variable (SNVT) for common totals shown on the System-10-LON BTU Meter.

VOLUME TOTAL

System-10 BTU Meter

Engineering Units

System-10 BTU

Meter

Multiplier

LonWorks SNVT and

Transmitted

Engineering Units

Maximum Total Transmitted

Over the Network

Gallons

X 100

SNVT_vol_f – Liters

3,785,411,621 Liters

Liters

X 1000

SNVT_vol_f – Liters

9,999,999,000 Liters

X 1

SNVT_vol_f – Liters

9,999,999,000 Liters

ENERGY TOTAL

System-10 BTU Meter

Engineering Units

System-10 BTU

Meter

Multiplier

LonWorks SNVT and

Transmitted

Engineering Units

Maximum Total Transmitted

Over the Network

Btu

X 10k

SNVT_Btu_f – Btu

99,999,990,000 Btu

kWhr

X 10

SNVT_Btu_f – Btu

341,214,065,900 Btu

Tonhr

X 1

SNVT_Btu_f – Btu

119,999,998,000 Btu