beautypg.com

ONICON FB-3500 Series User Manual

Page 23

background image

11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]
FB-3500 Bi-Directional Insertion Electromagnetic Flow Meter Manual 05/14 - 0718-3

Page 23

4.1 HELPFUL HINTS FOR START-UP AND COMMISSIONING

A step-by-step procedure and companion worksheet are located on the next two pages. Please
read all installation instructions carefully before proceeding with installation, start-up and
commissioning.

1.

ONICON flow meters are individually calibrated for a particular application. Be

sure to verify the pipe size and location.

2.

The electronic flow sensing systems will not work in air.

3.

When measuring analog output signals, remember that current (mA) must be

measured in series, while voltage is measured in parallel. If the 4-20 mA signal

is already connected to a control system, you must break the connection and

measure the signal in series.

4.

When measuring frequency outputs in Hz, take your multimeter out of “autorange

mode” and manually set the range for a voltage level above 15 VDC. This will

prevent false readings when signal is not present.

5.

All wiring connections should be made at the end of the factory cable. Do not

attempt to remove the factory installed cable or change the orientation of the

electronics enclosure.

6.

Never connect power to analog or frequency output signal wires. ONICON FB-3500

flow meters are not “loop powered” devices.

SECTION 4.0: START-UP & COMMISSIONING FOR ONICON

INSERTION ELECTROMAGNETIC FLOW METERS

This manual is related to the following products: