Steam Distributors Installation Manual | 6

Figure 5: Long Steam Run

GO TO

C2

- 45º

2

+ 45º

1

1 turn

3

B

Always align distributor holes so that steam is

discharged upwards to ensure condensate will

remain in the distributor.

Figure 6: Vertical Airflow

1 ft (30 cm)
min before turn

Condensate

tee every

15-20 ft

(4.5 - 6 m)

Condensate

tee at low

points

Individually trap multiple condensate

returns before joining on common line.

To Drain

Install condensate tee

before distributor

Method for Longer Runs With Limited Vertical Space

1 ft (30 cm)

min.