3 | Steam Distributors Installation Manual

Table 1:. Steam Line Material

Steam Hose

Copper Tube

Stainless Steel Tube

Short run < 10 feet (3 m)

Long run > 10 feet (3 m)

Di / RO water


Table 2: Recommended Material And Size For Steam Run

Load

Steam run

Steam line material

Steam line description

lb/hr

kg/hr

ft

m

0-30

0-13

0-10

0-3

Copper tube

¾” med-l tubing (7/8” o.d.)

0-30

0-13

10+

3+

Copper tube

1” med-l tubing (1 1/8” o.d.)

0-30

0-13

0-10

0-3

Stainless steel tube 7/8” tube x 0.049” thick

0-30

0-13

10+

3+

Stainless steel tube 1 1/8” tube x 0.49” thick

30-100

13-45

0-20

0-6

Copper tube

1 ½” med-l tubing (1 5/8” o.d.)

30-100

13-45

20+

6+

Copper tube

2” med-l tubing (2 1/8” o.d.)

30-100

13-45

0-20

0-6

Stainless steel tube 1 3/4” tube x 0.065” thick

30-100

13-45

20+

6+

Stainless steel tube 2” tube x 0.065” thick

Please note that options shown in a bold-italic font requires that reducers be used at both ends. These extra
large sizes are to allow for better condensation removal in long steam runs. These sizes cannot be
connected to either the humidifier or distributor using the supplied hose couplings.


Table 3: Recommended condensate line at distributor(s)

Dispersion Method

Condensate Hose

Copper Tube

Stainless Steel Tube

1 x steam
distributor

3/8”

Nortec 1328840

1/4” med-l tubing

(3/8” o.d.)

3/8” tube

0.049” thick

3 x steam
distributor

3/8”

Nortec 1328840

1/2” med-l tubing

(7/8” o.d.)

5/8” tube

0.049” thick

*when using more than one distributor, the condensate line should be trapped before joined together.