Nortec Steam Distributors User Manual
Page 6
3 | Steam Distributors Installation Manual
Table 1:. Steam Line Material
Steam Hose
Copper Tube
Stainless Steel Tube
Short run < 10 feet (3 m)
Long run > 10 feet (3 m)
Di / RO water
Table 2: Recommended Material And Size For Steam Run
Load
Steam run
Steam line material
Steam line description
lb/hr
kg/hr
ft
m
0-30
0-13
0-10
0-3
Copper tube
¾” med-l tubing (7/8” o.d.)
0-30
0-13
10+
3+
Copper tube
1” med-l tubing (1 1/8” o.d.)
0-30
0-13
0-10
0-3
Stainless steel tube 7/8” tube x 0.049” thick
0-30
0-13
10+
3+
Stainless steel tube 1 1/8” tube x 0.49” thick
30-100
13-45
0-20
0-6
Copper tube
1 ½” med-l tubing (1 5/8” o.d.)
30-100
13-45
20+
6+
Copper tube
2” med-l tubing (2 1/8” o.d.)
30-100
13-45
0-20
0-6
Stainless steel tube 1 3/4” tube x 0.065” thick
30-100
13-45
20+
6+
Stainless steel tube 2” tube x 0.065” thick
Please note that options shown in a bold-italic font requires that reducers be used at both ends. These extra
large sizes are to allow for better condensation removal in long steam runs. These sizes cannot be
connected to either the humidifier or distributor using the supplied hose couplings.
Table 3: Recommended condensate line at distributor(s)
Dispersion Method
Condensate Hose
Copper Tube
Stainless Steel Tube
1 x steam
distributor
3/8”
Nortec 1328840
1/4” med-l tubing
(3/8” o.d.)
3/8” tube
0.049” thick
3 x steam
distributor
3/8”
Nortec 1328840
1/2” med-l tubing
(7/8” o.d.)
5/8” tube
0.049” thick
*when using more than one distributor, the condensate line should be trapped before joined together.