beautypg.com

Installing on the curb – Nortec SETC Outdoor User Manual

Page 14

background image

11 | Installation

Table 4: SETC Roof Curb Depth (Dimension A)

Model

A (Inside Curb Depth)

In (cm)

100

8.6 (28 cm)

175

8.6 (28 cm)

250

15 (38 cm)

375

15 (38 cm)

525

30.6 (78 cm)

750

30.6 (78 cm)

1050

46.3 (118 cm)

Installing on the Curb

 If desired sealing material such as caulking or a gasket can be laid on the top of the curb

prior to lifting the SETC into place.

 Use the removable lugs installed in the base of the humidifier to lift it into place. Ensure

that the cable/chain/straps used for lifting do not come into contact with and damage the
cabinet. The inside skirt of the base must fit inside the roof curb.

 To secure the SETC in place remove the four lifting lugs and insert shims or blocks to fill any

gap between the outside skirt of the base and the curb. Drive screws through the four holes
to secure the unit to the curb.

 If the building is positively or negatively pressured the pipe chase opening or the roof curb

opening should be closed around the piping to prevent the building drawing cold air in or
exhausting warm air out through the SETC cabinet.















Figure 7: Installing on the Curb

Cross section of curb and cabinet base from right side

Inside Skirt

Outside Skirt

Pipe Chase

Insert wood

block

Screw to

Curb

Remove lifting

lugs

Roof Curb

Cabinet Base