Niveo Professional NPD8C16A User Manual
Page 12
![background image](https://www.manualsdir.com/files/799766/content/doc012.png)
MS-PDU User Manual V/0
12
Note:1. Click RESET button, product will restart.
2.Click BUTTON and RESET at the same time, will restore the factory setting.
3.Buzzing will not alarm while restarting and restoring the factory setting.
6.2.2 SNMP Access
The software supports SNMP v1. A MIB file is provided with an enterprise number.
OID table as below.
Item
OID
Description
Mode
Device Name
1.3.6.1.4.1.30966.10.2.1.1
Name of the device
Read/Write
Device Type
1.3.6.1.4.1.30966.10.2.1.2
Type of the device
Read/Write
Output Num
1.3.6.1.4.1.30966.10.2.1.3
Number of outlets
Read
Input Voltage
1.3.6.1.4.1.30966.10.2.2.1
Input voltage
Read
Input Current
1.3.6.1.4.1.30966.10.2.2.2
Input ampere
Read
Output Current1
1.3.6.1.4.1.30966.10.2.3.1
Ampere of outlet No.1
Read
Output Current2
1.3.6.1.4.1.30966.10.2.3.2
Ampere of outlet No.2
Read
Output Current3
1.3.6.1.4.1.30966.10.2.3.3
Ampere of outlet No.3
Read
Output Current4
1.3.6.1.4.1.30966.10.2.3.4
Ampere of outlet No.4
Read
Output Current5
1.3.6.1.4.1.30966.10.2.3.5
Ampere of outlet No.5
Read
Output Current6
1.3.6.1.4.1.30966.10.2.3.6
Ampere of outlet No.6
Read
Output Current7
1.3.6.1.4.1.30966.10.2.3.7
Ampere of outlet No.7
Read
Output Current8
1.3.6.1.4.1.30966.10.2.3.8
Ampere of outlet No.8
Read
Output Current9
1.3.6.1.4.1.30966.10.2.3.9
Ampere of outlet No.9
Read
Output Current10
1.3.6.1.4.1.30966.10.2.3.10
Ampere of outlet No.10
Read
Output Current11
1.3.6.1.4.1.30966.10.2.3.11
Ampere of outlet No.11
Read
Output Current12
1.3.6.1.4.1.30966.10.2.3.12
Ampere of outlet No.12
Read
Output Current13
1.3.6.1.4.1.30966.10.2.3.13
Ampere of outlet No.13
Read
Output Current14
1.3.6.1.4.1.30966.10.2.3.14
Ampere of outlet No.14
Read
Output Current15
1.3.6.1.4.1.30966.10.2.3.15
Ampere of outlet No.15
Read
Output Current16
1.3.6.1.4.1.30966.10.2.3.16
Ampere of outlet No.16
Read