INSTALLATION (cont.)

Drain Hose Connection (cont.)

Check following items:

• No kinks or bends on the drain hose
• No trap in the drain hose
• The end of the drain hose should be highter than the water level at the drain
• No dripping from the drain hose at the clamping area
• When uninstalling the unit, empty the drain pan by draining out the water through

the condensate pan drain pipe.

CAUTION: For the gravitational drain, make sure that DIP switch #2

of DSW3 on the relay board is set to the ON position (see “DIP

Switch Configuration and Setting” on page 22). The condensate

water will drain out from the drain pipe of the condensate pan.

Packing Attachment

Apply the provided packing to the cool air

exhaust to prevent condensation in high

humidity environments.

Remove the liner on the packing and

attach the packing to cover the edge of the

duct flange to avoid cool air leaking

through the gap.

UNIT

SLOPE

ABOVE
DRAIN
WATER

NO TRAP
TO DRAIN HOSE

UNIT

NO TRAP

NO POOL

PACKING

EDGE of DUCT FLANGE