INSTALLATION (cont.)
Drain Hose Connection (cont.)
Check following items:
• No kinks or bends on the drain hose
• No trap in the drain hose
• The end of the drain hose should be highter than the water level at the drain
• No dripping from the drain hose at the clamping area
• When uninstalling the unit, empty the drain pan by draining out the water through
the condensate pan drain pipe.
CAUTION: For the gravitational drain, make sure that DIP switch #2
of DSW3 on the relay board is set to the ON position (see “DIP
Switch Configuration and Setting” on page 22). The condensate
water will drain out from the drain pipe of the condensate pan.
Packing Attachment
Apply the provided packing to the cool air
exhaust to prevent condensation in high
humidity environments.
Remove the liner on the packing and
attach the packing to cover the edge of the
duct flange to avoid cool air leaking
through the gap.
UNIT
SLOPE
ABOVE
DRAIN
WATER
NO TRAP
TO DRAIN HOSE
UNIT
NO TRAP
NO POOL
PACKING
EDGE of DUCT FLANGE