STEP 2: Prepare The Venting System

Standard Fittings

NOTE:

If the existing duct is round, you must use a rectangular-to-round adapter, with a rectangular 3” extension
duct installed between the damper assembly and the adapter to prevent the exhaust damper’s sticking.

Duct Length

The total length of the duct system, including straight duct, elbows, transitions, and wall or roof caps

must not

exceed the equivalent of 140 feet

.

For best performance, do not use more than three 90 degree elbows, and keep length as short as possible.

Below are the standard fittings and their equivalent length in feet.

Figure 9

To calculate the equivalent length of each duct piece used, see the examples below.

Examples

For 3 1/4”x10” SYSTEMS

1-transition

=

5 ft.

2-90° elbows

= 20 ft.

1-Wall Cap

= 40 ft.

8 feet straight

=

8 ft.

TOTAL LENGTH

= 73 ft.

1-3 1/4” x 10” 90° elbow =

25 ft.

1-Wall Cap

=

40 ft.

8 feet straight duct

=

8 ft.

TOTAL LENGTH

=

73 ft.

For 6” ROUND SYSTEMS