11 Device Information

1

Type and order code

LI 11MER

2

Design

2.1

Model

Reversible

2.2

Degree of protection according to EN 60 529

IP 21

2.3

Installation location

Indoors

3

Performance data

3.1

Operating temperature limits:

Heating water flow/return flow

°C / °C

Up to 58 / above 18

Cooling, flow

°C

+7 to +20

Air (heating)

°C

-25 to +35

Air (cooling)

°C

+15 to +40

3.2

Temperature spread of heating water

at A7 / W35

K

9.6

5.0

3.3

Heat output / COP

at A-7 / W35

1

kW / ---

1. This data indicates the size and capacity of the system. For an analysis of the economic and energy efficiency of the system, other parameters, such as, in particular, the defrosting

capacity, the bivalence point and regulation, should also be taken into consideration. The specified values, e.g. A2 / W55, have the following meaning: External temperature 2 °C
and heating water flow temperature 55 °C.

7.5 / 2.8

7.0 / 2.7

at A-7 / W45

1

kW / ---

6.8 / 2.3

at A2 / W35

1

kW / ---

8.9 / 3.4

8.8 / 3.3

at A7 / W35

1

kW / ---

11.1 / 4.2

11.1 / 4.0

at A7 / W45

1

kW / ---

9.4 / 3.5

at A10 / W35

1

kW / ---

12.1 / 4.6

12.0 / 4.4

3.4

Temperature spread of cooling water

at A35 / W7

K

6.5

5.0

3.5

Cooling capacity / COP

at A27 / W7

kW / ---

8.8 / 2.8

8.8 / 2.8

at A27 / W18

kW / ---

10.9 / 3.3

10.8 / 3.2

at A35 / W7

kW / ---

7.6 / 2.1

9.5 / 2.5

at A35 / W18

kW / ---

9.5 / 2.5

9.5 / 2.5

3.6

Sound power level device / outdoors

dB(A)

55 / 61

3.7

Sound pressure level at a distance of 1 m (indoors)

dB(A)

50

3.8

Heating water flow with an internal pressure differential of m³/h / Pa

1.0 / 3000

1.9 / 10900

3.9

Cooling water flow with an internal pressure differential ofm³/h / Pa

1.0 / 3000

1.3 / 5900

3.10 Air flow rate with an external static pressure differential of m³/h / Pa

4200 / 0

m³/h / Pa

2500 / 25

3.11 Refrigerant; total filling weight

Type / kg

R404A / 3.6

4

Dimensions, connections and weights

4.1

Device dimensions

H x W x L cm

136 x 75 x 88

4.2

Device connections to heating system

Inch

G 1 1/4'' external

4.3

Air duct inlet and outlet (min. internal dimensions)

L x W cm

50 x 50

4.4

Weight of the transportable unit(s) incl. packing

kg

205

5

Electrical Connection

5.1

Nominal voltage; fuse protection

V / A

230 / 25

5.2

Nominal power consumption

1

A2

W35

kW

2.61

2.67

5.3

Starting current with soft starter

A

38

5.4

Nominal current A2 W35 / cos

ϕ

A / ---

14.2 / 0.8

14.5 / 0.8

6

Complies with the European safety regulations

2

2. See CE declaration of conformity

7

Additional model features

7.1

Defrosting

Automatic

Type of defrosting

Reverse cycle

Defrosting tray included

Yes (heated)

7.2

Heating water in device protected against freezing

Yes

3

3. The heat circulating pump and the heat pump controller must always be ready for operation.

7.3

Performance levels

1

7.4

Controller internal/external

External