2. Pressurize supply piping system by either

opening propane/LP supply tank valve for

propane/LP gas or opening main gas valve

located on or near gas meter for natural gas,

or using compressed air.

3. Check all joints from gas meter to equipment

shutoff valve for natural gas or propane/LP sup-

ply to equipment shutoff valve for propane/LP

(see Figures 22 and 23). Apply noncorrosive

leak detection fluid to all joints. Bubbles form-

ing show a leak.

4. Correct all leaks at once.

CHECKING GAS CONNECTIONS

WARNING: Test all gas piping

and connections, internal and

external to unit, for leaks after

installing or servicing. Correct

all leaks at once.

WARNING: Never use an

open flame to check for a leak.

Apply a noncorrosive leak detec-

tion fluid to all joints. Bubbles

forming show a leak. Correct all

leaks at once.

CAUTION: Make sure exter-

nal regulator has been installed

between propane/LP supply and

fireplace. See guidelines under

Connecting Fireplace to Gas

Supply, page 14.

PRESSURE TESTING GAS SUPPLY
PIPING SYSTEM
Test Pressures In Excess Of 1/2 PSIG
(3.5 kPa)
1. Disconnect fireplace with its main gas valve

(control valve) and equipment shutoff valve

from gas supply piping system. Pressures

in excess of 1/2 psig will damage fireplace

regulator.

2. Cap off open end of gas pipe where equipment

shutoff valve was connected.

3. Pressurize supply piping system by either

opening propane/LP supply tank valve for

propane/LP gas or opening main gas valve

located on or near gas meter for natural gas,

or using compressed air.

4. Check all joints of gas supply piping system.

Apply noncorrosive leak detection fluid to all

joints. Bubbles forming show a leak.

5. Correct all leaks at once.
6. Reconnect fireplace and equipment shutoff

valve to gas supply. Check reconnected fittings

for leaks.

Test Pressures Equal To or Less Than
1/2 PSIG (3.5 kPa)
1. Close equipment shutoff valve (see Figure 21).

INSTALLATION

Continued

Figure 21 - Equipment Shutoff Valve

Figure 23 - Checking Gas Joints for

Propane/LP Gas

Propane/LP
Supply Tank

Figure 22 - Checking Gas Joints for

Natural Gas

Gas Control Valve

Equipment Shutoff Valve

Equipment Shutoff Valve

Gas Meter

Gas Control Valve

PRESSURE TESTING FIREPLACE GAS
CONNECTIONS
1. Open equipment shutoff valve (see Figure 21).
2. Open main gas valve located on or near gas

meter for natural gas or open propane/LP

supply tank valve.

Open

Closed

Equipment
Shutoff
Valve