Adjusting the settings with the remote control
If necessary, the sensor settings can be adjusted as follows:
Shut off the water supply. In order to adjust the sensor with the remote control,
hold the remote control straight in front of the sensor in a distance of about
6-8” (15-20cm). Choose the function you want to adjust by pressing once on
the function buttons. After pressing once on a specific function button, a
quick flashing of the red light at the front of the sensor will occur. At this stage,
you can change the setting by pressing the (+) or the (-) buttons, every push will
increase or decrease one level. After finishing the adjustment, turn the water
supply back on.
DETECTION RANGE This faucet was supplied with a Self Adjusting
Sensor. The ideal detection range for the
location will be
set automatically.
Only if necessary, use the remote control to adjust the sensor
range as follows:
Press the RANGE button. Wait until a quick flashing of the red light of
the sensor eye is perceived. Then, press + to increase the delay out
time and – to reduce it. Every push will increase or decrease one
level.
ENTRANCE TO THE SELF ADJUSTMENT MODE
Check that no objects are in front of the sensor.
Press the ADJ button. Once a quick flashing of the red light of the
sensor eye is perceived, remove your hand holding the remote
control and move away from the sensor area. The ideal sensor
range for the specific location will be set automatically.
Once the self adjustment has taken place the solenoid valve will be
opened and closed for 1 second as an indication that the ideal sensor
range was set and the product is ready for use.
SECURITY TIME The Security time, prevents continuous running
of water due to reflections or vandalism. By default, if the sensor
is covered for more than 90 seconds the water flow will shut
automatically. To resume regular operation any obstruction must be
removed.
Press the SEC button. Wait until a quick flashing of the red light of the
sensor eye is perceived. Then, press + to increase the security time
and – to reduce it.