III. INSTALLATION INSTRUCTIONS

Allowable Operating Conditions:

Ambient Temperature: 40ºF - 120ºF (4ºC - 50ºC)

Ambient Relative Humidity: 0% to 90%

Line Voltage: -15% to +10% of Nominal

Frequency: 50/60 Hz.

Supply Water Temperature: 40ºF-100ºF (4ºC-38ºC)

Supply Water Pressure: 20-100 psig

Supply Water Conductivity:

• 70-1000 mincromho (on-off control)

• 200-1000 micromho (prop or P + I control)

(See Figure 30 & 31 on page 27 for alternative water conditions)

Maximum Duct Static Pressure: 5” MDM, 7” MDS/MDD

units

NOTE: If units are mounted in outdoor enclosures, conditions

inside enclosure must be maintained as shown above.

Mounting

The cabinet is designed to safely contain the working com-

ponents of the Herrtronic MD humidifier and dissipate heat to

protect the electronics. Herrtronic MD Series electronic steam

humidifiers, room distribution units, steam pipes, and any ac-

cessories should be located in a manner to facilitate routine in-

spection and any necessary maintenance. The unit should not

be located above (such as false ceilings) or around valuable

property, where a malfunction could cause damage. Correct

positioning of the Herrtronic MD humidifier is important to allow

for proper operation and easy maintenance. Minimum clearance

around the cabinet should be maintained as follows:

Unit Clearances By Model

Unit Series

MDM

5-30 Lbs.

MDS

10-100 Lbs.

MDD

110-250 Lbs.

Left

2”

2”

2”

Right

20”

20”

20”

Top

12”

12”

12”

Bottom

10”

10”

10”

Four lag bolts, (2) 5/16” and (2) 1/4”, are supplied with the MDS

and MDM units which are designed to be secured to a wall. In-

stall the top two lag bolts (5/16”) according to the dimensions in

Figure 1. Hang the unit on the wall, and then install the bottom

two lag bolts (1/4”) and secure all four bolts. Be sure the unit is

level and mounted directly to the wall to wood studs at least 2”

thick (or equivalent).

Operating weights are as follows:

• MDM - 82 lbs.

• MDS - 131 lbs.

• MDD - 258 lbs.

WARNING!

Do not mount any controls inside the unit or tap power from

any location in the unit, except as stated in these instruc-

tions. Do not place objects near the cabinet. Do not attach

to dry wall without studs.

NOTE

To mount the Room Distribution Unit, refer to the “supple-

mental” RDU Installation Instructions.

Plumbing

To make the necessary connections for water fill and drain,

the following steps are required: (refer to Figure 2 for drain

location)

1. Install an external shutoff valve between the water supply

and the humidifier for ease in servicing the unit.

2. Connect water supply to 1/4” compression fitting on the

bottom of the cabinet.

CAUTION!

Do not use reverse osmosis or demineralized water treatment

without first consulting the factory. This water may not be suf-

ficiently conductive to allow proper operation. Consult factory

if water is outside the range of allowable conductivities. Do

not use hot water.

5.25

16.00

4.25

22.38

4.00

1.81

21.89

1.81

16.00

1.50

1.50

21.56

1.82

MDS

MDM

Ø .38" x Ø .75"

Keyhole Slot

Typ.

.75 Typ.

Both units

Ø .25 Typ.

5-30#

10-100#

Figure 1