beautypg.com

Relative humidity, Types of control time – Herrmidifier Herrtronic MD User Manual

Page 5

background image

Herrtronic

®

MD Series

I n s t a l l a t i o n , O p e r a t i o n , & M a i n t e n a n c e M a n u a l

5

www.herrmidifier-hvac.com

Types of Control

The Herrtronic MD System is available with (3) types of con-

trol ---(1) On/Off, (2) Proportional, (3) Proportional + Integral:

1. On/Off – Humidity is sensed by a humidistat that pro-

vides an On/Off input to the humidifier. Humidity varies

above and below the setpoint based on the tolerance

and accuracy of the humidistat.

2. Proportional – A proportional controller produces a sig-

nal (ohms, volts DC, or milliamps DC) corresponding to

the difference between the control humidity and the hu-

midity setpoint. The humidifier’s output increases as this

difference (and signal) increases. Humidity variations

will be smaller than with “On/Off” control and the control

humidity will be maintained within the bandwidth, toler-

ance, and accuracy of the controller.

3. Proportional + Integral – Over a repeating time period

the “P+I” control simply evaluates the difference be-

tween the average control humidity and the control hu-

midity setpoint and adjusts the bandwidth to minimize

the “offset.” Optimal control is attained in most cases

with this alternative.

NOTE

If your application is unique or water is excessively

“clean” or “dirty,” consult Herrmidifier for assis-

tance in matching your humidifier, water treatment,

and its control scheme to your application!

40

Relative Humidity %

0

5

10

15

20

25

30

35

40

45

50

55

45

50

55

60

Types of Control

Time

Offset Correction

On/Off Control

Proportional Control

Proportional + Integral Control

Set Point

P + I Bandwith