Herrmidifier Herrtronic MD User Manual
Page 27
Herrtronic
®
MD Series
I n s t a l l a t i o n , O p e r a t i o n , & M a i n t e n a n c e M a n u a l
27
www.herrmidifier-hvac.com
Inputs / Outputs of Terminal Strips and Terminal Block
Terminal Block
Position 1-6
24 RET (GND)
7-12
24 VAC
All twelve (12) positions should be utilized if the Room Dispersion Unit (RDU) is installed
RDU Terminal Strip – Connections to RDU only
Pole
1
24 RET (GND) (Always)
2
24 VAC Trigger (24 VAC when contactor is energized)
3
Line Voltage (Always)
4
Line Voltage (Always)
5
24 VAC Air (24 VAC when switch Proving Switch is closed)
6
24 VAC (Always)
Control Terminal Strip
Pole
1
24 VAC (Always)
2
Airflow / High Limit input, 24 VAC for operation
3
External “Off”, 24 VAC for operation
4
Control input ground – Modulating and on/off
5
Control input signal – Modulating and on/off
6
+5 VDC
7
+20 VDC
8
Limit input ground - Modulating
9
Limit input signal - Modulating
10
+5 VDC
11
RS-485 Communication, Negative, Digital
12
RS-485 Communication, Positive, Digital
Figure 30
Hard Water/Softened Water*
(750-1000 Micromho)
Adjust Menu Items to These Settings
MDM
MDS/
MDD
Cycle Time (Menu #3)
75
115
Low Drain Threshold (Menu #2)
88
84
Capacity Setpoint (Menu #2)
96
96
High Drain Threshold (Menu #3)
108
108
*Naturally soft water is less than 50 micromho.
Figure 31
Very Hard Water
(> 1000 Micromho)
Adjust Menu Items to These Settings
MDM
MDS/
MDD
Cycle Time (Menu #3)
60
100
Low Drain Threshold (Menu #2)
91
86
Capacity Setpoint (Menu #2)
94
92
High Drain Threshold (Menu #3)
105
105