B114lp typical wiring diagrams, 2151 photoelectronic detector specifications – Greenheck No Flow Duct Smoke Detector (System Sensor) User Manual

Page 2

background image

A05-1018-004

B114LP Typical Wiring Diagrams

B114LP Base Terminals
No. Function

1

Remote Annunciator (+)

2 Not

Used

3 Not

Used

4

Remote Annunciator (–)

5 Not

used

6 N.O. Supervisory

Relay

7

N.O.

Form A Contacts

8 N.O. Alarm

Relay

9 N.O. Form

A

10 C.

Initiation

11 C.

Contacts

12 N.O. Alarm

Relay

13 N.C. Form

C

14 C.

Auxiliary

Contacts

2151 Photoelectronic Detector Specifications

Architectural/Engineering Specifications

The air duct smoke detector shall be a System Sensor model 2151 Series Smoke detector UL listed to UL 268A specifically for use in air handling systems when
used in conjunction with the B114LP (120 VAC) base or the B114LPBT (24VAC/DC) base. The detector shall operate at air velocities up to 3000 feet per minute.
It shall be capable of local testing via magnetic switch or remote testing using the UL listed RTC100 Remote Test Coil accessory with the RTS151 Remote Test
Station. It shall be capable of providing duct smoke detector status via the UL listed model APA151 Piezo Annunciator.

Physical Specifications

Electrical/Operating Specifications

Size

1.66˝ (4.22cm) H, 6.1˝ (155mm) dia. flanged base

Operating Voltage/Alarm Current

See Base Specifications

Weight

3.6 oz. (104 g)

Standby current

85 μA maximum

Operating Temperature Range

32˚F to 120˚F (0˚C to 49˚C)

Sensitivity

3%±.7% / ft.

Operating Humidity Range

10 to 93% RH non-condensing

Air Velocity Rating

0 to 3000 fpm

Construction

Flame retardant thermoplastic

B114LP/B114LPBT Adapter Base Specifications

Electrical Specifications

Loop Type

4-wire

Current Limit Resistor

Yes

Alarm Contact Type

Form A&C + A supply

Nominal Voltage

B114LP: 120 VAC; B114LPBT: 24VAC/DC

Alarm Current (mA)

75 mA AC Max.

Relay Contact Ratings

Resistive or Inductive (60% power factor) load. Form A: 2.0A at 30 VAC/DC; Form C: 0.6A at 110VDC, 2.0A at 30VDC;
1.0A at 125VAC, 2.0A at 30VAC

B114LP/B114LPBT Junction Box Specifications

Box depth contingent on base and wire size. Refer to National Electric Code or local applicable codes for appropriate recommendations.

Single Gang

3½˝ Octagon

4˝ Octagon

4˝ Square

50mm

60mm

75mm

No

No

Yes

Yes

No

No

No

RA100Z
(Optional)

RA100Z
(Optional)

RELEASING
DEVICE

POWER

RELEASING
DEVICE

POWER

1

6

7

8

9

10

11

12

13

14

2

3

4

5

RELEASING
DEVICE

1

6

7

8

9

10

11

12

13

14

2

3

4

5

EOL

FIRE

ALARM

CONTROL

PANEL

ALARM INITIATION LOOP

SPECIFIED
BY PANEL
MANUFACTURER

BLACK LEADS
TRANSFORMER
PRIMARY

120 VAC

120 VAC

(+)

(–)

(+)

(–)

RA100Z
(Optional)

FAN/DAMPER
CONTROL

POWER

1

6

7

8

9

10

11

12

13

14

2

3

4

5

EOL

FIRE

ALARM

CONTROL

PANEL

ALARM INITIATION LOOP

SPECIFIED
BY PANEL
MANUFACTURER

BLACK LEADS
TRANSFORMER
PRIMARY

120 VAC

S0279-01

S02809-01