Page 7

background image

Centrifugal Roof Exhaust Fans

7

®

PROBLEM

CAUSE

CORRECTIVE ACTION

Reduced Airflow

System resistance too high

Check system for proper operation of backdraft or
control dampers; remove obstructions in ductwork, etc.

Unit running backwards

See Pre-Starting Checks.

Fan speed too low

Increase fan speed.

Excessive dirt buildup on wheel

Clean wheel.

Improper wheel alignment

Center wheel on inlets.

Excessive Noise
or Vibration

Bad Bearings

Replace.

Belts too tight or too loose

Refer to Figure 4 and adjust tension.

Wheel improperly aligned and
rubbing

Center wheel on inlets. See Figure 1.

Loose drive or motor pulleys

Align and tighten. See Pre-Start-up Checks.

Foreign objects in wheel or housing

Remove objects, check for damage or unbalance.

Unbalance of wheel caused by
excessive dirt and grease buildup

Remove buildup.

Job Information

Job Name: ___________________________________

Service Organization: ______________________________

Address: _____________________________________

Address: _________________________________________

City: ________________________________________

City: _____________________________________________

State:

_______________ Zip:

__________________

State:

____________ Zip:

__________________________

Phone: ______________________________________

Phone: ___________________________________________

Contact Person: ______________________________

Work Done By: ____________________________________

Nameplate Information

Field Start-Up Documentation

Model: ______________________________________

Volts:

_________ Hertz:

________ Phase:

______

Actual

Voltage:

_________ Hertz:

_____ Phase:

_____

Amps: _______________ Mark: ________________

Actual Amperage: _________________________________

Supply hp: ___________ Exhaust hp: ___________ Blower

Rotation:

__________________________________

Serial Number: _______________________________

Air Volume:

Design cfm: _________________________

Model Voltage: _______________________________

Actual cfm: __________________________

Motor Amperage: _____________________________

Level of fan (L or H): _______________________________

Fan RPM: ______________________________________

Fan RPM Range (min.) ____________ (max.) ___________

Maintenance Documentation

WARNING

Before taking any corrective action, make certain unit
is not capable of operation during repairs.

AVERTISSEMENT

Avant d’entreprendre toute action corrective, s’assurer
que l’appareil ne pourra pas fonctionner durant les
réparations.

Troubleshooting