Greenheck, Warranty, Maintenance – Greenheck CUE (457692) User Manual
Page 2: Troubleshooting, Replacement parts
IOM CUE FS
Rev. 3 February 2001
NOTE: Each fan bears a manufacturer’s nameplate with model number and serial number embossed. This information
will assist the local Greenheck representative and the factory in providing service and replacement parts.
CAUSE
CORRECTIVE ACTION
System resistance too high.
Check system: Proper operation of
backdraft or control dampers,
obstruction in ductwork, etc.
Unit running backwards.
Correct as shown in Fig. 2.
Excessive dirt buildup on wheel.
Clean wheel.
Improper wheel alignment.
See Fig. 1 and Pre-Starting Checks.
Wheel improperly aligned and rubbing.
See Fig. 1 and Pre-Starting Checks.
Foreign objects in wheel or housing.
Remove objects, check for damage.
Unbalance of wheel caused by excessive
Remove buildup.
dirt and grease buildup.
REDUCED
AIRFLOW
PROBLEM
EXCESSIVE
NOISE OR
VIBRATION
Maintenance
Motor maintenance is generally limited to cleaning and lubrication (where applicable). Cleaning should be limited to exterior
surfaces only. Removing dust buildup on motor housing ensures proper motor cooling. Greasing of motors is only intended
when fittings are provided. Many fractional motors are permanently lubricated and should not be lubricated after installation.
Motors supplied with grease fittings should be greased in accordance with manufacturers’ recommendations. With motor
temperatures under 104°F (40°C), the grease should be replaced after 2000 hours of running time as a general rule.
Wheels require very little attention when moving clean air. Occasionally, oil and dust may accumulate causing imbalance.
When this occurs, the wheel and housing should be cleaned to ensure smooth and safe operation.
All fasteners should be checked for tightness each time maintenance checks are performed prior to restarting unit.
A proper maintenance program will help these units deliver years of dependable service.
Troubleshooting
NOTE: Before taking any corrective action, make certain unit is not capable of operation during repairs.
Replacement
Parts
MOTOR
SHOCK
MOUNTS
WHEEL
BREATHER
TUBE
BIRDGUARD
*CURB CAP /
VENTURI
CONDUIT
CHASE
HOOD
*WINDBAND
*VERTICAL
SUPPORTS
*DRAIN
TROUGH
*For replacement, the windband, vertical supports, drain trough and curb
cap/venturi come as one complete assembly.
GREENHECK
P.O. BOX 410 SCHOFIELD, WISCONSIN 54476-0410
PH. 715-359-6171
www.greenheck.com
®
Warranty
Greenheck warrants this equipment to be free from defects in material and workmanship for a period of one year from the purchase
date. Any units or parts which prove defective during the warranty period will be replaced at our option when returned to our
factory, transportation prepaid.
Motors are warranted by the motor manufacturer for a period of one year. Should motors furnished by Greenheck prove defective
during this period, they should be returned to the nearest authorized motor service station. Greenheck will not be responsible for
any removal or installation costs.