6. Individual damper sections, as well as entire multiple section assemblies must be

completely square and free from racking, twisting, or bending. Measure diagonally
from upper corners to opposite lower corners of each section.

7. Damper blades, axles, and linkage must operate without binding. Before system

operation, cycle dampers after installation to assure proper operation. On multiple
section assemblies, all sections should open and close simultaneously.

SAFETY DANGER !

Electrical input may be needed for
this equipment. This work should be
performed by a qualified electrician.

Electrical Guidelines

SAFETY CAUTION !

Verify power requirements before wiring

actuator. Greenheck is not responsible for

any damage to, or failure of the unit caused

by incorrect field wiring.

Electrical and/or pneumatic connections to damper actuators should be made in accordance with wiring and piping

diagrams developed in compliance with applicable codes, ordinances and regulations.

Connect electrical connection to terminal strip as shown on drawing (see figure 1).

Installation - cont...

Do not twist
or bow. Mount
damper plumb
in the opening.

A

B

AF = BE
AB = CD

C

D

E

F

HIGH PRESSURE (UP STREAM)

LOW PRESSURE

(DOWN STREAM)

120 VAC ONLY

L1 L2

1-ACTUATOR HOT (ACT 1)
2-ACTUATOR NEUTRAL (ACT 2)
3-ACTUATOR POSITION COMMAND (ACT 3)
4-FLOW OUTPUT (+)

7-FLOW/POSITION SETPOINT (-)

6-FLOW/POSITION SETPOINT(+)

5-FLOW OUTPUT (-)

9-THERMISTOR (-)

8-ACTUATOR POSITION FEEDBACK (ACT5)

12-CONTACT CLOSURE

11-CONTACT CLOSURE

10-THERMISTOR (+)

Fig.1 wiring diagram