Damper troubleshooting, Damper maintenance, Our commitment – Greenheck Heavy Duty Smoke Damper HSD-401 (464604) User Manual

Page 3

background image

Damper does not
fully open and/or fully
close

Damper does not
operate

Damper troubleshooting

The following is a possible cause and correction list for common concerns with the dampers.

Damper maintenance

Dampers do not typically require maintenance as long as they are kept dry and clean. If cleaning is necessary, use mild
detergents or solvents. If lubrication is desired for components such as axle bearings, jackshaft bearings, and jamb seals, do
not use oil-based lubricants or any other lubricants that attract contaminants such as dust.

Dampers and their actuator(s) must be maintained, cycled, and tested in accordance with:
• The latest editions of NFPA 80, 90A, 92A, UL864, and local codes.
• Actuator manufacturer recommendations.

symptom

Possible Cause

Corrective Action

Frame is ‘racked’ or not round causing

Adjust frame such that it is square

blades to bind on jamb seals or frame

and plumb or round where applicable

Actuator linkage loose

Close damper, disconnect power, adjust

and tighten linkage

Defective motor

Replace

Screws in damper linkage

Locate screws and remove

Contaminants on damper

Clean with a non-oil-based solvent

(see Damper Maintenance)

No power supplied to the actuator

464604• HSD Rev. 4, October 2012

Copyright 2012 © Greenheck Fan Corporation

As a result of our commitment to continuous improvement, Greenheck reserves the right to change

specifications without notice.

Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in

the Library under Warranties.

®

Phone: (715) 359-6171 • Fax: (715) 355-2399 • E-mail: [email protected] • Website: www.greenheck.com

Our Commitment