Damper Troubleshooting

Problem

Possible Cause

Solution

Damper does not move

Damper linkage failed

Inspect damper for failed clevis pins, clevises, or
crankarms and replace as necessary.

Obstruction in damper linkage
or inside duct

Inspect for projecting mounting bolts, debris inside
damper and remove.

Damper attempts to
move but does not open
fully

Obstruction in damper linkage
or inside duct

Inspect for projecting mounting bolts, debris inside
damper and remove.

Damper linkage modified in the
field

Readjust linkage so blade rotates fully open and
closed.

Linkage pivots failed

Replace linkage bars, clevises and pins as required.

High noise level

Very high velocity/flow

Reduce flow through damper.

Damper not closing fully

Readjust drive linkage to fully close damper.

The following is a cause and correction list for common concerns with the damper: