beautypg.com

Installation instructions ehh-601d – Greenheck EHH-601D, Flange/Sleeve Installation (474641) User Manual

Page 2

background image

2

Maximum Size and Installation Information

Model EHH-601D is a Miami-Dade Qualified and Florida Product Approved louver and must be installed in accordance with the

installation instructions shown herein. Model EHH-601D is qualified for installation within concrete/masonry, steel stud, structural

steel or wood framed building conditions. Model EHH-601D is structurally calculated to withstand positive and negative wind-loads

up to 150 PSF. The maximum single section rough opening width is 72.50 in. The maximum single section rough opening height

is 144.50 in. While the maximum rough opening height is limited to 144.50 in., the rough opening width is limited to 1,000 in. as

multiple sections may be installed side by side in accordance with installation instructions.

Minimum Rough

Opening Size

12 in. W x 7 in. H

Maximum Single Section

Rough Opening Size

72.50 in. W x 144.50 in. H

Installation Instructions

eHH-601D

Florida Product Approval No: FL10088

Miami-Dade NOA No.: 12-0830.08

Maximum Wind-load: 150 PSF

Flange/Sleeve Installation

Building Condition/Substrate Limitations

• All wood substrate shall be G= 0.55 density or better
• All metal stud substrate should be min. 16 Ga. FY= 50 KSI
• All structural steel substrate shall be min. 0.25 in. thick FY= 36 KSI
• All concrete substrate shall be min. 3000 PSI
• Concrete masonry shall be ASTM C90, Type II, 2000 PSI, grout-filled