Installation instructions ehh-601d, Structure depth – Greenheck EHH-601D, Channel Installation with VCD-40 Damper (474644) User Manual
Page 6
6
Installation Instructions
eHH-601D
Florida Product Approval No: FL10088
Miami-Dade NOA No.: 12-0830.08
Maximum Wind-load: 150 PSF
Channel Installation
with VCD-40 Damper
Single Section
CMU / Concrete Substrate
• Min. structure depth 6.866 in.
• Max. structure depth infinite
Steel Stud / Structural Steel Substrate
• Min. structure depth 5.866 in.
• Max. structure depth infinite
Structure Depth
FASTENER SCHEDULE (FIELD INSTALLED - NOT BY GREENHECK)
CONCRETE
CMU
STEEL
MIN.
FASTENER TYPE
ALL FASTENERS ARE STEEL OR STAINLESS
JAMB PERIMETER ANGLE FASTNER
DIAMETER
# RQD.
CENTERS
EDGE
EMBED.*
X
2KSI
SCOTS TAPCON / TAPCON
1/4
VARIES
4.750
1.500
1.750
X
4KSI
SCOTS TAPCON / TAPCON
1/4
VARIES
6.000
1.500
1.750
X
1.5KSI
SCOTS TAPCON / TAPCON
1/4
VARIES
3.000
1.500
1.750
X
65KSI Fy
BOLT/NUT OR TAPPING SCREW
1/4
VARIES
6.000
0.500
0.125
MULLION END PLATE FASTENER, HEIGHT <=144
DIAMETER
# RQD.
CENTERS
EDGE
EMBED.*
X
2KSI
SCOTS TAPCON / TAPCON
1/4
9/END
2.000
1.500
1.625
X
4KSI
SCOTS TAPCON / TAPCON
1/4
8/END
2.000
1.500
1.625
X
65KSI Fy
BOLT/NUT OR TAPPING SCREW
1/4
8/END
1.000
0.500
0.125
MULLION ANGLE MOUNT FASTENER, HEIGHT <=144
DIAMETER
# RQD.
CENTERS
EDGE
EMBED.*
CENTER
X
2KSI
SCOTS TAPCON / TAPCON
1/4
32/ANG.
2.000
1.500
1.750
3.375
X
4KSI
SCOTS TAPCON / TAPCON
1/4
27/ANG.
2.000
1.500
1.750
3.375
X
1.5KSI
SCOTS TAPCON / TAPCON
1/4
32/ANG.
2.000
1.500
1.750
3.375
X
65KSI Fy
BOLT/NUT OR TAPPING SCREW
1/4
16/ANG.
1.000
0.500
0.125
3.000
X
65KSI Fy
BOLT/NUT OR TAPPING SCREW
1/4
11/ANG.
1.000
0.500
0.188
3.000
X
65KSI Fy
BOLT/NUT OR TAPPING SCREW
1/4
16/ANG.
1.000
0.500
0.188
3.766
MULLION END PLATE FASTENER, HEIGHT <=96
DIAMETER
# RQD.
CENTERS
EDGE
EMBED.*
X
2KSI
SCOTS TAPCON / TAPCON
1/4
6/CAP
2.000
1.500
1.750
X
4KSI
SCOTS TAPCON / TAPCON
1/4
6/CAP
2.000
1.500
1.750
X
65KSI Fy
BOLT/NUT OR TAPPING SCREW
1/4
3/CAP
1.000
0.500
0.125
MULLION ANGLE MOUNT FASTENER, HEIGHT <=96
DIAMETER
# RQD.
CENTERS
EDGE
EMBED.*
CENTER
X
2KSI
SCOTS TAPCON / TAPCON
1/4
11/ANG.
2.000
1.500
1.750
3.375
X
4KSI
SCOTS TAPCON / TAPCON
1/4
9/ANG.
2.000
1.500
1.750
3.375
X
1.5KSI
SCOTS TAPCON / TAPCON
1/4
11/ANG.
2.000
1.500
1.750
3.375
X
65KSI Fy
BOLT/NUT OR TAPPING SCREW
1/4
7/ANG.
1.000
0.500
0.125
3.766
X
65KSI Fy
BOLT/NUT OR TAPPING SCREW
1/4
6/ANG.
1.000
0.500
0.125
3.000
* EMBEDMENT DEPTH IS EQUAL TO OVERALL FASTENER LENGTH FOR CONCRETE/CMU FASTENERS. IF SHIMS ARE USED, FASTENER LENGTH MUST BE INCREASED BY THICKNESS OF SHIMS.
• REFERENCE SUBSTRATE DEPTH CHART TO DETERMINE IF MULLION ANGLE IS REQUIRED.