Crankarm Orientation and Actuator Assembly
Location for Counter Clockwise Fail Rotation

Actuator Assembly is fastened to the mounting
plate through one of these holes

Crankarm Orientation and Actuator Assembly
Location for Clockwise Fail Rotation

B

B

90°

90°

1.938

1.938

Instructions:

These installation instructions assume the damper is already
mounted in a duct or sleeve with the damper shaft extending
beyond the duct or sleeve 6 inches.

1. Install the stand off bracket.

Dampers with a jackshaft

1a. Mount the stand off bracket onto the jackshaft

bracket with (4)

1

/

4

-20 X

1

/

2 in

. thread cutting screws, #16.

Orient the anchor bracket perpendicular to the damper on

the duct or sleeve so that the bracket's shaft hole is

centered on the jackshaft.

Dampers without a jackshaft (Shaft Extension)

1b. Mount the stand off bracket spanning across the damper

frame flanges. Orient the anchor bracket perpendicular to

the damper on the duct or sleeve so that the bracket's

shaft hole is centered on the shaft extension. Fasten to

the damper frame with (4) #14 Tek screws or equal,

supplied by others. Be sure not to run the screws into the

damper linkage, which is between the flanges.

2. Mount the actuator and all factory assembled actuator

parts to the mounting bracket (#13) with the (2)

5

/

16 in.

-18

hex nuts supplied on the actuator assembly. Attach the

assembly to the bracket using the post (#3) through the

hole illustrated to the right on the diagram that

corresponds to the correct fail direction.

Note: All fail rotations refer to the damper shaft rotation

needed to achieve the desire blade fail position. Inspect

the damper blades and the damper shaft to determine the

proper damper shaft rotation for the desired blade fail

position.

3. Mount the mounting bracket to the stand off bracket

using (4)

1

/

4 in.

-20 x

1

/

2 in.

bolts, #11, and (4)

1

/

4 in.

- 20

Spinlock nuts, #12, included with this kit. Use the outer

four holes of the mounting bracket for jackshafted models

and the inner four holes for directly driven models.

Note: The mounting bracket may be attached in three

positions: parallel with the duct, perpendicular up from the

duct, or perpendicular down from the duct. Choose a

position that offers the most clearance for the application.

4. Note the damper shaft rotation for fail direction and

position the crankarm in one of the positions shown in the

illustrations to the right. Do not tighten the crankarm to

the damper shaft.

5. Attach the crankarm to the clevis on the actuator with the

clevis pin, #9, and the hitchpin cotter, #10, through the

hole labled “B” to the right. Position the damper blades in

the desired fail position (open or closed). Tighten the

crankarm to the damper shaft.

Orientation of Stand Off

Bracket for a directly

driven damper

Orientation of Stand Off

Bracket for a jackshaft

driven damper

Copyright © 2006 Greenheck Fan Corporation

454201 Siemens #3 Rev. 4 October 2006

SIEMENS #3

INSTRUcTIoNS

6. Run the supply pressure to the actuator and regulate

it to a maximum of 25 psi.

7. Apply air pressure to the actuator.

The damper blades should fully open or close

and return to the fail position when power is
disconnected, if they do not, adjustments can
be made by resetting the crankarm position on
the damper or actuator shaft or by changing the
distance from the actuator face to the center of the
hole in the clevis.