Leak Detection Kit quick setup guide (rev.131111B-GD)

3

RELAY MODE jumper:

Controls the behavior of the output relays when a leak-detection or cable-fault event
occurs. In “supervised” mode, both relays are energized when conditions normal, and
de-energize when an alert occurs; in “non-supervised” mode, the relays are de-energized
when conditions are normal, and energized when an alert occurs. This action is illustrated
by the diagrams below: (Note that the terms “normally open” (NO) and “normally
closed” (NC), when describing relay actions, refer to the state of the relay contacts in the
relay’s “normal”, i.e. de-energized state, not to “normal” as in normal room conditions!
)

NON-

SUPERVISED

MODE

SUPERVISED

MODE

(recommended)

with no alarm condition,

both relays are

de-

energized

, and the NC

contact pairs are closed.

with no alarm condition,

both relays are

energized

, and the NO

contact pairs are closed.

when water is detected
on the cable, the LEAK

relay

energizes

, and its

NO contact pair closes

when water is detected
on the cable, the LEAK

relay

de-energizes

, and

its NC contact pair closes

if a cable fault is

detected, the FAULT

relay

energizes

, and its

NO contact pair closes

if a cable fault is

detected, the FAULT

relay

de-energizes

, and

its NC contact pair closes

LOW

(alarms on 6” (152mm)

of wetted cable)

HIGH

(alarms on 0.5”

(13mm) of wetted cable)

MEDIUM

(alarms on 2” (51mm)

of wetted cable)

SENSITIVITY jumper:

Adjusts the sensitivity to dampness along the detection cable. The default setting is

low, which is generally sufficient for detecting spills from broken pipes or overflowing
tanks; however, if your particular application involves smaller leaks, such as from an
air-conditioner’s drip pan, the medium or high sensitivity settings may be required instead.
Higher sensitivity may also be required if you need to detect leaks of distilled or deionized
water, or other fluids which are only weakly conductive. You may need to experiment to
find the best setting for your particular requirements. (Note: if you change this jumper
setting, you must power-cycle the LD300 for it to recognize the change.
)

contact pair is closed

NC

NC

NO

NO

C

C

FAULT

LEAK

(no alarm condition)

X

X

X

contact pair is open

NC

NC

NO

NO

C

C

FAULT

LEAK

leak detected

X X

NC

NC

NO

NO

C

C

FAULT

LEAK

cable fault

X

X

NC

NC

NO

NO

C

C

FAULT

LEAK

(no alarm condition)

X

X

NC

NC

NO

NO

C

C

FAULT

LEAK

leak detected

X

X

NC

NC

NO

NO

C

C

FAULT

LEAK

cable fault

X X