beautypg.com

Remote outlet switching (rcm-o and rcu-o only), Actions – Geist RCX Series v3 User Manual

Page 42

background image

GM1111

42

Revision Date 4/3/2014

Remote Outlet Switching (RCM-O and RCU-O Only)


Actions

The RCM-O and RCU-O Series are equipped with individually switchable outlets. There are
seven possible actions for any given outlet, available from the “Action” drop down box on the
Actions tab of the Control page:

Figure 46: Outlet Actions

On – Immediate: Turns on all selected outlets with no delay.

On – Delayed: Turns on all selected outlets with applicable delays.

Off – Immediate: Turns off all selected outlets with no delay.

Off – Delayed: Turns off all selected outlets with applicable delays.

Reboot: Cycles power to the selected outlets with one applicable delay. Each outlet is
powered-down immediately, then “Reboot Duration” sets the delay after power-down and
before power-up.

Reboot-Delayed: Cycles power to the selected outlets with two applicable delays.
“Reboot” delays before power down, and “Reboot Duration” sets the delay after power-down
and before power-up.

Reset kWh: Resets the kWh total on all selected outlets to 0. (RCU-O only)

Cancel Actions: Cancels any actions currently in progress on the selected outlets.

Figure 47: Outlet Action Confirmation


To perform an action, select the check box next to the outlets needing attention, select an
action from the drop down box and click the “Execute” button. A dialog box will appear asking
for confirmation of the selected actions. Click OK to execute the action. Click cancel to make
changes or ignore the action.

Note: “Reboot”, Reboot-Delayed” and “On/Off-Delayed” actions are subject to the delays set on the
Settings Tab of the Control page.

This manual is related to the following products: