Specifications, Overview, Environmental – Geist RCX Series v3 User Manual
Page 4: Electrical, Receptacle ratings, Networking
GM1111
4
Revision Date 4/3/2014
Specifications
Overview
The RCM-O, RCU-O, RCO and RCX series units are rack level PDUs with circuit monitoring via a
built-in web server. In the RCX series, built-in sensors monitor Voltage, Current, instantaneous
and cumulative Power, as well as calculated Power Factor. The RCM-O series units have all
these sensors plus outlet level switching. The RCO series units have the same built-in sensors
as the RCX plus outlet level current and power monitoring, while RCU-O series units have all of
the RCX sensors plus outlet level switching plus current and power monitoring. Web pages,
including graphs, are generated by the unit to monitor power and environmental conditions
within the cabinet. No software other than a web browser is required for operation and several
data formats are available. Optional external sensors and network cameras are also available.
These units can be built for installation in either Delta or Wye building wiring configurations.
Environmental
Temperature
Operating:
10°C (50°F) min
45°C (113°F) max
Storage:
-25°C (-13°F) min 65°C (149°F) max
Humidity
Operating:
5% min
95% max
(non-condensing)
Storage:
5% min
95% max
(non-condensing)
Elevation
Operating:
0 m (0 ft) min
2000 m (6561 ft) max
Storage:
0 m (0 ft) min
15240 m (50000 ft) max
Electrical
See nameplate for unit ratings.
Receptacle Ratings
NEMA 5-15R or L5-15R 125 Volts, 15 Amp
NEMA 5-20R or L5-20R 125 Volts, 20 Amp
NEMA 6-20R or L6-20R 250 Volts, 20 Amp
NEMA L5-30R
125 Volts, 30 Amp
NEMA L6-30R
250 Volts, 30 Amp
NEMA L15-30R
250 Volts (3 phase), 30 Amp
IEC-320 C13
125/250 Volt, 15 Amp (per Receptacle Bank)
IEC-320 C19
125/250 Volt, 20 Amp
Networking
Protocols
HTTP, HTTPS (SSL/TLS), SMTP, POP3, ICMP, DHCP, TCP/IP, NTP, Telnet, Syslog
Ethernet Link Speed