Example: AC cable
If overlength AC or DC cables are to be laid
in loops in the connection area, attach the
cables with cable ties to the eyelets provi-
ded on the top and bottom of the connec-
tion block.
Maximum fuse
rating on alternat-
ing current side
Inverter
Phases
AC power
Maximum
fuse rating
Recommended
fuse rating
Fronius Symo 10.0-3-M
3
10000 W
1 x C 63 A
1 x C 25 A
Fronius Symo 12.5-3-M
3
12500 W
1 x C 63 A
1 x C 32 A
Fronius Symo 15.0-3-M
3
15000 W
1 x C 63 A
1 x C 32 A
Fronius Symo 17.5-3-M
3
17500 W
1 x C 63 A
1 x C 40 A
Fronius Symo 20.0-3-M
3
20000 W
1 x C 63 A
1 x C 50 A
NOTE! Local regulations, the energy supply company or other factors may re-
quire an earth-leakage circuit breaker in the grid line. For this situation, a type A
earth-leakage circuit breaker with a tripping current of at least 100 mA is generally
adequate. In particular cases, and depending on local factors, however, the type
A earth-leakage circuit breaker may trip at the wrong time. For this reason, Fron-
ius recommends that an earth-leakage circuit breaker that is suitable for frequen-
cy converters should be used.
max. C 63 A
AC ~
RCD
National Standards
?
Type A
YES
I
ΔN
≥ 100 mA
§