Fronius String Control 250/25 DCD DF User Manual
Page 63

5
EN-US
Abbreviations
and Descripti-
ons Used
DC cable ‘OUT’
DC output cable from Fronius String Control 250/25
DCD DF to inverter.
The polarity of the ‘OUT’ DC cable results from the
connection specification of the ‘IN’ DC cable.
DC cable ‘IN’
Solar module strings from the solar modules to the
Fronius String Control 250/25 DCD DF.
Each solar module string has one DC+ cable and one
DC- cable.
Max. input voltage in no-load operation
600 V
Max. input current
250 A
Max. input current per fuse holder
20 A
Max. number of strings (with integrated solar module fuse)
25
Max. cable cross section for terminals on the
1 - 25 mm²
solar module side for rigid wires
Max. cable cross section for terminals on the
1 - 16 mm²
solar module side for flexible wires
Important ! For a wire cross section smaller than 2.5 mm², use wire ferru-
les.
Max. cable diameter of ‘IN’ DC cable
7 mm
Min. cable diameter of ‘IN’ DC cable
2 mm
Max. cable cross section for the M12 connections on the
120 mm²
inverter side
Number of measuring channels
5
Max. current per measuring channel
50 A
Screw joint for cable attachment to the solar module side
M16
Screw joint for cable attachment to the inverter side
M40 / M32
Protection type
IP 55
Protection class
II
Ambient conditions
-25°C - +55°C
-13°F -
+131°F
Dimensions (without screw joints)
754 x 571 x 216 mm
29.69 x 22.48 x 8.50 in.
DATCOM power supply
via Solar Net
optional via a 12 V power supply
Max. Solar Net current consumption
110 mA
Weight
18,4 kg
Technical Data